Table 16 — Trip Messages for 50BV VFD (cont)

ERROR

CODE

COMMUNICATION

NO.

PROBLEM

POSSIBLE CAUSES

REMEDIES

OP3

C

Overvoltage during
constant-speed
operation

• The input voltage fluctuates abnormally.
(1) The power supply has a capacity of

200kVA or more.

(2) A power factor improvement capacitor is

opened or closed.

(3) A system using a thyristor is connected

to the same power distribution line.

• The motor is in a regenerative state

because the load causes the motor to run at
a frequency higher than the inverter
output frequency.

• Insert a suitable input reactor.

• Install a dynamic braking resistor.

OL1

D

Inverter overload

• The acceleration ACC time is too short.
• The DC braking amount is too large.
• The V/F setting is improper.
• A restart signal is input to the rotating

motor after a momentary stop, etc.

• The load is too large.

• Increase the acceleration time ACC.
• Reduce the DC braking amount F251

and the DC braking time F252.

• Check the V/F parameter setting.
• Use F301 (auto-restart) and F302

(ride-through control).

• Use an inverter with a larger rating.

OL2

E

Motor overload

• The V/F setting is improper.
• The motor is locked up.
• Low-speed operation is performed

continuously.

• An excessive load is applied to the motor

during operation.

• Check the V/F parameter setting.
• Check the load (operated machine).
• Adjust OLN to the overload that the

motor can withstand during operation in a
low speed range.

*EPHO

9

Output phase failure

• A phase failure occurred in the output line

of the main circuit.

• Check the main circuit output line, motor,

etc., for phase failure.

• Enable F605 (Output phase failure

detection).

*EPH1

8

Input phase failure

• A phase failure occurred in the input line

of the main circuit.

• Check the main circuit input line for phase

failure.

• Enable F608 (input phase failure

detection).

OH2

2Eh

External thermal trip

• A thermal trip command is entered from

an external input device.

• Check the external input device.

*Ot

20h

Over-torque trip

• The load torque rises up to the over-torque

detection level during operation

• Enable F615 (Over-torque trip selection)
• Check whether the system is in a normal

condition.

OLr

F

Dynamic braking

resistor overload trip

• The deceleration time is too short.
• The dynamic braking amount is too large.

• Increase the deceleration time dEC.
• Use a dynamic resistor with a larger

capacity (W) and adjust F308 (PBR
capacity parameter) accordingly.

OH

10h

Overheat

• The cooling fan does not rotate.
• The ambient temperature is too high.
• The vent is blocked up.
• A heat generating device is installed close

to the inverter.

• The thermistor in the unit is broken.

• Restart the operation by resetting the

inverter after it has cooled down enough.

• The fan requires replacement if it does

not rotate during operation.

• Secure sufficient space around the

inverter.

• Do not place any heat-generating device

near the inverter.

• Make a service call.

*UP1

1E

Undervoltage trip
(main circuit)

• The input voltage (in the main circuit) is

too low.

• Check the input voltage.
• Enable F627 (undervoltage trip

selection).

• To cope with a momentary stop due to

undervoltage, enable F302 (ride-through
control) and F301 (auto-restart).