Configuration Screens (cont)

*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.

Maintenance Screens

DESCRIPTION

VALUE*

UNITS

NAME

OMNIZONE::VPTESTC: Field Test
Field Test

Reschedule Rate

5

sec

RESCHRAT

Power on Delay

40

sec

RESCHPOR

OMNIZONE::MODECTRC: Mode Control
Determines Heat

Reschedule Rate

10

sec

RESCHRAT

Power on Delay

30

sec

RESCHPOR

Run Fan in Bypass

Reschedule Rate

10

sec

RESCHRAT

Power on Delay

30

sec

RESCHPOR

Water Economizer Control

Reschedule Rate

10

sec

RESCHRAT

Power on Delay

30

sec

RESCHPOR

Mod Valve & Econo

Reschedule Rate

2

sec

RESCHRAT

Power on Delay

10

sec

RESCHPOR

OMNIZONE::SETSYNCC: Setpoint Synchronization
Setpoint Synch

Reschedule Rate

3

sec

RESCHRAT

Power on Delay

10

sec

RESCHPOR

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

OMNIZONE::ADAPT01: VAVRESET Software point control
Analog Output Point

0

%

Value

Status Point

Off

Value

Occupied ?

No

Status

Reset Point

0

dF

Value

Controlling Setpoint

0

dF

RefOut

Control Point

0

dF

Value

PID_Master_Loop

Reference Output

0

%

RefOut

Proportional Term

0

%

PTerm

Integral Term

0

%

ITerm

Derivative Term

0

%

DTerm

Integrator Flags

100

Flags

Task Timer

6

sec

TaskTimr

OMNIZONE::ADAPT02: Head Pressure control
Analog Output Point

100

%

Control

Value

Status Point

Off

Control

Value

Occupied ?

No

Status

Reset Point

0

PSIG

Value

Controlling Setpoint

0

PSIG

RefOut

Control Point

117.72

PSIG

Value

PID_Master_Loop

Reference Output

0

%

RefOut

Proportional Term

0

%

PTerm

Integral Term

0

%

ITerm

Derivative Term

0

%

DTerm

Integrator Flags

100

Flags

Task Timer

2

sec

TaskTimr

OMNIZONE::ADAPT03: Building Pressure Ctrl.
Analog Output Point

0

%

Value

Status Point

Off

Value

Occupied ?

No

Status

Reset Point

0

ma

Value

Controlling Setpoint

12.32

ma

RefOut

Control Point

12.44

ma

Value

PID_Master_Loop

Reference Output

0

%

RefOut

Proportional Term

2

%

PTerm

Integral Term

0

%

ITerm

Derivative Term

0

%

DTerm

Integrator Flags

100

Flags

Task Timer

3

sec

TaskTimr