7.1

Two Door Configuration Connections

This configuration assumes JP12 is OFF, configuring the Satellite board for Two-Door control.

7.1.1

Output Relays

Please refer to Figure 4 on page 4 for output relay wiring locations.

See page 6 for a sample Fail-Safe Door Lock Output Relay drawing.
See page 6 for a sample Fail-Secure Door Lock Output Relay drawing.
See page 6 for a sample Alarm Output Relay drawing.
See page 7 for a sample Door Held Open – A-Door Relay drawing.
See page 7 for a sample Door Held Open – B-Door Relay drawing.
See page 8 for a sample General Purpose Normally-Open Output Relay drawing.
See page 8 for a sample General Purpose Normally-Closed Output Relay drawing.

Table 2: Output Relays

TB-7/TB-10 Relay Outputs

Description

TB-7 – Pin 1

lock output – normally open line

TB-7 – Pin 2

common/ground

TB-7 – Pin 3

lock output – normally closed line

TB-7 – Pin 4

alarm output – normally open line

TB-7 – Pin 5

common/ground

TB-7 – Pin 6

alarm output – normally closed line

TB-10 – Pin 1

GPO 3/DHO-B

a

– normally open line

a. The Door Held Open (DHO) alarm feature is not available in

16-bit Doors software applications.

TB-10 – Pin 2

common/ground

TB-10 – Pin 3

GPO 3/DHO-B

a

– normally closed line

TB-10 – Pin 4

GPO 4/DHO-A

a

– normally open line

TB-10 – Pin 5

common/ground

TB-10 – Pin 6

GPO 4/DHO-A

a

– normally closed line