Wiegand Elevator Control Panel

2305 Bering Drive

01942-001 Rev. D

San Jose, CA 95131 USA
(800) 260-5265 (408) 435-8400 FAX (408) 577-1792
Web: www.kerisys.com E-mail: [email protected]

Page 10 of 24

Quick S

tart Guide

LC-502W/LC-508W

5.1

Connecting Wires - Removing Terminal Blocks

Follow the instructions in Figure 5 when connecting wires to the controller or when removing
terminal blocks from the controller.

Figure 5: Connecting Wires and Removing Terminal Blocks

5.2

LC-502W Wiring Connections

The following connections are made to install the LC-502W Elevator Control panel (see Figure 3
on page 8).

Floor Control Relay

RS-485 Controller Network

Reader/Amplifier Daisy-Chain

Earth Ground and Power

5.2.1

Floor Control Relay

The Floor Control Relay is connected to the door controls at the elevator panel. If a controller has
an SB-500 Satellite Board attached to control two floors, connect the lower floor to the A-Floor
Control Relay and connect the higher floor to the B-Floor Control Relay. Make the floor control
relay connections per the information in Table 1 and Figure 6 on page 11.

Table 1: Floor Control Relay

Connection

LC-500W TB-3 Pin

SB-500 TB-7 Pin

Description

1

Normally-Open

2

Common

3

Normally-Closed

Advertising