LAARS Mighty Therm2 MT2P (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 5

Advertising
background image

MT2P Pool Heater

Page 5

Figure 1. Dimensional Data.

AIR

VENT

SHIPPING

UNIT

CONN.

CONN.

WEIGHT

1

SIZE

A

B

C

D

E

F

W

V

LBS kG

500

33¾ 85

16¾ 43

17

10 25

8 20

46¼ 117 6 15

8 20

425 193

750

45¾ 116

22¾ 53

17

10 25

24

58¼ 148 6 15

10 25

505 229

1000

57¾ 147

28¾ 73

17

10 25

24

70¼ 178 8 20

10 25

615 279

1250

68¼ 173

34

87

10¼

26

10 25

9 23

80¾ 205 8 20

12 30

675 306

1500

78¾ 200

39½ 100

10¼

26

10 25

9 23

91¼ 232 8 20

12 30

760 345

1750

89¼ 227

44¾ 113

10¼

26

10 25

9 23

101¾ 258

8 20

12 30

825 375

2000

99¾ 253

49¾ 127

10¼

26

10 25

9 23

112¼ 285 12 30

14 36

955 434

NOTES: 1. Add 55 lbs (25kg) for pump-mounted units.

Dimensions in

inches cm.

in the appliance has/have sufficient power to pull air

and vent properly when the following guidelines for

horizontal air and vent are followed (

see Table 1

).

NOTE: On all MT2P models, the vent collar size is

larger than the size of the vent pipe that can be used.

Side wall vent terminals for these sizes are shipped

with replacement vent collars, to accommodate

horizontal vent sizes. Vent collar size and horizontal

pipe diameters can be found in Table 1. The larger vent

collar size is to accommodate Category I (vertical) vent

systems.
NOTE: When located on the same wall, the MT2P

combustion air intake terminal must be installed a

minimum of 12" (30cm) below the exhaust vent terminal

and separated by a minimum of 36 inches (91cm)

horizontally.

The air intake terminal must be installed high enough

to avoid blockage from snow, leaves and other debris.

Never obtain combustion air from the pool area. Corrosion

of and/or damage to the pool heater may result.