LAARS Mighty Therm2 MT2P (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 9

Advertising
background image

MT2P Pool Heater

Page 9

Canada, from CSA B149.1 as well as all applicable

local codes, it is required that installers provide some

means to prevent operation with a blocked common

vent. It is suggested that a blocked vent safety system

be employed such that if the switch from one appliance

trips due to excessive stack spill or backpressure

indicating a blocked vent condition, that all appliances

attached to the vent be locked out and prevented

from operating. (Note that the MT2P Pool Heater

is equipped with a blocked vent safety (pressure)

switch, as shipped.) As an additional precaution, it is

recommended that a Carbon Monoxide (CO) alarm be

installed in all enclosed spaces containing combustion

appliances. If assistance is required in determining

how a blocked vent safety system should be connected

to a LAARS product, please call Laars' Applications

Engineering Dept.

Refer to the installation and operating instructions

on all appliances to be common vented for instructions,

warnings, restrictions and safety requirements. If safe

operation of all appliances connected to a common vent

cannot be assured, including prevention of spillage of

flue gasses into living spaces, common venting should

not be applied, and appliances should each be vented

separately.

2.2.4 Category III Vent

When the MT2P is vented with horizontal

discharge, it must be installed per this installation

manual and the venting system manufacturer’s

installation instructions. The vent system must be

sealed stainless steel, per

Table 5

.

Route the vent pipe to the heater as directly as

possible. Seal all joints and provide adequate hangers

as required in the venting system manufacturer’s

Installation Instructions. Horizontal portions of the

venting system must be supported to prevent sagging

and may not have any low sections that could trap

condensate. The unit must not support the weight of

the vent pipe. Horizontal runs must slope downwards

not less than ¼ inch per foot (2 cm/m) from the unit to

the vent terminal.

Reference Table 1

for the size of the

Category III vent system. Up to three elbows can be

used with 50 linear feet (15.2m) of pipe. Subtract 10

allowable linear feet (3.0m) for every additional elbow

used.

2.3 Locating Vent & Combustion Air

Terminals

2.3.1 Side Wall Vent Terminal

The Laars side wall vent hood (

listed in Table

1

) must be used when the heater is vented through a

side wall. It provides a means of installing vent piping

through the building wall, and must be located in

accordance with ANSI Z223.1/NFPA 54 and applicable

local codes. In Canada the installation must be in

accordance with CAN/CGA B149.1 or .2 and local

applicable codes (

see Figure 3

). Consider the following

when installing the terminal:

1. Through-the-wall vent terminals must terminate at

least 7-feet above a public walkway.

2. Locate the vent terminal so that vent gases cannot

be drawn into air conditioning system inlets. The

National Fuel Gas Code requires that it be at least

3 feet (0.9m) above any such inlet

that is within a horizontal distance of 10 feet (3m).

3. Locate the vent terminal so that vent gases cannot

enter the building through doors, windows, gravity

inlets or other openings. The National Fuel Gas

Code requires that it be located at least 4 feet

(1.2m) below, 4 feet (1.2m) horizontally from,

or 1 foot (0.3m) above such openings. Whenever

possible, locations under windows or near doors

should be avoided.

4. Locate the vent terminal so that it cannot be

blocked by snow. The National Fuel Gas Code

requires that it be at least 12 inches (30 cm) above

grade, but the installer may determine it should be

higher, depending upon local conditions.

5. Locate the terminal so the vent exhaust does

not settle on building surfaces and other nearby

objects. Vent products may damage such surfaces

or objects.

6. Locate the terminal at least 6 feet (1.8m)

horizontally from any gas or electric metering,

regulating, or relief equipment.

7. If the MT2P uses ducted combustion air from

an intake terminal located on the same wall,

locate the vent terminal at least 3 feet (0.9m)

horizontally from the combustion air terminal,

and locate the vent terminal at least 1 foot (0.3m)

above the combustion air terminal.

8. Note that side wall vent terminals for all models

are shipped with reducers for the vent collars,

TERM

DESCRIPTION

Pipe

Must comply with UL Standard 1738

such as Type 29-4C Stainless Steel

(either insulated or non-insulated).

Joint

Follow vent manufacturer’s instructions

Sealing

Table 5. Required Horizontal Venting Material.

OUTDOOR VENT

OUTDOOR

SIZE

TERMINAL

COMBUSTION

AIR TERMINAL

500

20254703

D2007900

750

20254705

D2007900

1000

20254705

D2008000

1250

D2007700

D2008000

1500

D2007700

D2008000

1750

D2007800

D2008000

2000

D2007800

D2008200

Table 6. Vent Terminals for Outdoor Units.

Advertising