LAARS Mini-Therm JVS (Sizes 50-225) - Install and Operating Manual User Manual

Page 19

Advertising
background image

Mini-Therm JV

Page 19

Figure 12. Typical Plumbing Diagrams.

JV

From

System

To

System

NON-LOW TEMPERATURE SYSTEMS

(120°F+ Return Temps)

Simple Primary/Secondary Piping - Hydronic - Not Low Temp

NOTE: All closed loop systems should include air elimination, expansion tank and feed water inlet. Place at point of lowest pressure (typically
at the inlet of pump).
NOTE: Ball valves should not be used as balancing valves. Only use for shutoff apps.

LOW TEMP SYSTEMS

JV

120°+

From

System

To

System

Primary/Secondary Piping with Variable Speed Injection

Variable Speed

Control

Pump

Pump

Isolation Valve

Isolation

Valve

The preferred piping configuration for JV boilers is always using primary/secondary piping.

There are some applications that are acceptable without primary/secondary piping, see below.

From

System

To

System

Primary/Secondary Piping with Field Balancing

(for Fixed Low Return Temperatures)

JV

Pump

Isolation Valve

Isolation

Valve

Balancing

Valve

Balancing

Valve

Pump

From

System

To

System

Tempering Valve with System Loop

and Boiler Loop Pump

JV

Pump

Isolation Valve

Isolation

Valve

Tempering

Valve

Pump

From

System

To

System

Primary/Secondary

System Loop with Tempering Valve and Pump with Boiler Loop

with Tempering Valve and Pump

JV

Pump

Isolation Valve

Isolation

Valve

Tempering

Valve

Pump

Tempering

Valve

Isolation

Valve

Isolation

Valve

Pump

Pump

JV

From

System

To

System

Primary/Secondary Piping with By-Pass

(for Fixed Low Return Temperatures)

Pump

Isolation

Valve

Pump

Isolation

Valve

Balancing

Valve

Balancing

Valve

Primary/Secondary Piping with Automatic By-Pass

Pump

Pump Isolation

Valve

Isolation

Valve

Auto

By-Pass

Valve

From

System

To

System

JV

JV

From

System

To

System

Primary/Secondary Piping with Laars

Thermostatic Union as an Automatic Bypass

Pump

Isolation

Valve

Pump

Isolation

Valve

Laars

Thermostatic

Union

PN 2400-030

Balancing

Valve

NOTE: All closed loop systems should include air elimination, expansion tank and feed water inlet. Place at point of lowest

pressure (typically at the inlet of pump).

NOTE: Ball valves should not be used as balancing valves. Only use for shutoff apps.

Advertising
This manual is related to the following products: