FielD COnneCtiOnS:
• remove VAri-PriMe Cover.
• remove the VAri-PriMe control box from the packaging and

familiarize yourself with each connection point.

1700 MBTU/h

and

1700 MBTU/h

1000 MBTU/h

• Locate the Blue and Black wires coming from

the top gas valve. Trace the wires to the spade
connection with the blue/white wire. Unplug the
connectors and insert the blue wire and connectors
from the VAri-PriMe unit.

• Locate the Blue and Black wires coming from the

bottom gas valve. Trace thse wires to the spade
connection with the Blue/White wire. Unplug
the connectors and insert the Blue/red wire and
connectors from the VAri-PriMe unit.

Photo 6

FIRMWARE SETTINGS
P = 20
I = 10
D = 0
ANTI RESET WINDUP = 600
CONTROL ERROR = 70

10K

R14 C12 R13 C11

-2

4V

INLET

SENSOR

1

2

3

4

1

2

3

4

1

2

3

2

3

4

4

1

1

2

3

2

4

6

8

1

3

5

7

1

3

5

7

+2

4V

6

8

SENSOR

2

4

10K OUTLET

JP5

TB1

7&8 = F

1&2 = SPARE JUMPER

TB2

TB5

TB4

TB6

PCB

DIGITIZED

P/N E2345200

LED1

JP1

7&8 = (Delta T) 30 DEG F / 16 DEG C

TB3

JP4

JP2

1&2 = (Delta T) 15 DEG F / 8 DEG C

3&4 = (Delta T) 20 DEG F / 10 DEG C

5&6 = (Delta T) 25 DEG F / 13 DEG C

JP3

N/C

COM

4-20MA(-)

4-20MA(+)

0-10VDC(+)

0-10VDC(-)

N/O

Figure 2

Terminal

Blocks

Jumpers