LAARS EDN Series - Installation, Operation and Maintenance Instructions User Manual

Page 4

Advertising
background image

Page 4

LAARS HEATING SYSTEMS

2.

The CSA standard C22.1 “Canadian Electrical
Code - Part 1” and local codes.

All vent installations must be made in accordance with:

1.

Part 7, Venting of Equipment of the National Fuel
Gas Code, ANSI 223.1 latest edition, or applicable
provisions of the local building codes or

2.

CAN/CGA B149.

When required by the jurisdiction authority, the

installations must conform to the American Society of
Mechanical Engineers' Safety Code for Controls and
Safety Devices for Automatically Fired Boilers, No.
CSD-1.

1.3 Unpacking the Appliance

Remove all packing and tie down materials.

Make immediate claims (to the carrier) if the appliance
and its packaging are damaged.

1.4 Locating the Appliance

The appliance is designed for installation on

combustible flooring, in alcoves, basements, closets, or
utility rooms. It must not be installed on carpeting. IF
INSTALLED IN A FINISHED AREA, PROVISION
SHOULD BE MADE FOR DRAINAGE OF ANY
ACCIDENTAL SPILLAGE OR LEAKAGE.

The location for the unit should be chosen with

regard to venting dimensions, convenient access to
piping, and accessibility for service and cleaning.

The boiler shall be installed so that the gas

ignition system components are protected from water
(dripping, spraying, rain, etc.) during appliance
operation or service (circulator replacement, control
replacement, etc.).

1.5 Clearances

The dimension and criteria in Table 1 should be

followed when choosing the location for the unit.

SECTION 2.
Venting Options

2.1 Direct Vent Kits

When using a direct vent kit, the appliance is a

sealed combustion unit. All of its air is drawn in from
the outside through the 5" outer pipe. Flue gases are
vented through the 3" vent pipe positioned inside the
5" intake pipe. The hot flue gases are surrounded by
the intake flow of cooler outdoor air. This vent system
may be installed through, and be in contact with,
combustible materials. Except for roof vent kit (max 7'
vertical) all venting should pitch away (down) from
unit.

2.2 Installing Direct Vent Kits

The direct vent appliance is certified with a

maximum of 15 linear feet (4.6m) of vent pipe and
three sets of elbows. There are two basic vent kits
available, together with various additional elbow and
extension kits if required (see Figures 3 and 4).
Detailed installation instructions are provided in the kits.

For additional length and/or fittings, the

following components are available:

3" and 5" elbow set

Part Number 2400-330

5" x 1' extensions

Part Number 2400-332

5" x 2' extensions

Part Number 2400-334

5" x 2' to 4' adjustable

extensions

Part Number 2400-336

3" x 1' extensions

Part Number 2400-338

3" x 2' extensions

Part Number 2400-340

3" x 2' to 4' adjustable

extensions

Part Number 2400-342

2.3 Locating the Vent on an Outside Wall

The center line of the vent opening must be at

least 16½" (419mm) above grade, outside, and at least
13½" (343mm) from any other building opening, such
as doors, windows, etc. Vent opening should be well
away from shrubbery or other obstructions that would
prevent free air flow to and from vent terminal. Do not
terminate vent under decks, stairways, or car ports.

NOTE: Should it be impossible to locate

opening center line 16½" (419mm) above grade, use
optional vent terminal extension (p/n 2400-278).

Vent terminals must also be at least 3' (0.9m)

above any forced air inlet located within 10' (3.0m),
and at least 7' (2.1m) above grade when located
adjacent to a public walkway, and cannot terminate in
a location where condensate or vapor may be a
nuisance, hazard, or could be a detriment to other
equipment. Vent terminals must have a minimum
clearance of 4' (1.2m) (6' (1.8m) in Canada)
horizontally from, and in no case above or below
electrical meters, gas meters, regulators, and relief
equipment unless a 4' (1.2m) horizontal distance is
maintained.

A.

Minimum clearance from combustible construction to
meet AGA/CGA requirements.

B.

Recommended clearance for accessibility and venting.

Table 1. Clearances

A

B

AGA/CGA

AGA

CGA

in.

mm

in.

mm

in.

mm

Left Side

1

25

6

152

24

610

Right Side

1

25

12

305

24

610

Top Side

1

25

14

356

24

406

Back

1

25

9

229

12

305

Front

1

25

24

610

24

610

Vent: Direct Vent

0

0

0

0

Vent: Category IV

3

76

3

76

Advertising