Category i, Non-category i – LAARS Mighty Max HH (Sizes 320M - 1000M) - Installation, Operation and Maintenance Instructions User Manual

Page 11

Advertising
background image

Mighty Max Hydronic Boiler

Page 11

Category I

Vertical Venting

with Ducted

Combustion Air

Horizontal Venting

Any Vent Which Does Not Meet

Category I Combustion Air

Through Louvers

Horizontal Venting

Ducted Combustion Air

(Certified As Direct Vent)

Non-Category I

Exhaust Terminal Detail

Side View

Wall

Figure 8. Venting and Combustion Air Options.

Vertical Venting (Category I)

Combustion Air In

Through Louvers

Side View

Wall

NOTE: All views are shown

from rear of heater

Horizontal

Intake Terminal Detail

(Combustion Air)

Screen Provided

On Vertical Intake

Air Terminal

For vertically ducted combustion air:
• Combustion air intake must

terminate at least 3 feet (0.91m)
lower than vent termination, if it is
located within a 10 foot (3.05m)
radius.

• Combustion air intake must be at

least 1 foot (0.3m) above roof top
and normal snow levels.