LAARS Mighty Therm LO-NOx PW (Sizes 500-1825) - Install and Operating Manual User Manual

Page 10

Advertising
background image

LAARS HEATING SYSTEMS

Page 10

Do not use water piping, fittings, valves, pumps,

and any other components which are not compatible
with potable water.

Do not connect the heater, which will be used to

supply potable water, to any heating system or
components previously used with a nonpotable water
heating system.

Do not add boiler treatment or any chemicals to

the heating system piping, since the piping contains
water for potable use.

Do not use solder containing lead in the potable

water lines.

Some jurisdictions may require a backflow

preventer in the cold water line. In such cases,
pressure relief valve may discharge water due to
expansion. An expansion tank approved for potable
water will eliminate this condition. Follow the
manufacturer's instructions for installation of the
expansion tank.

3.2.5 Piping System Requirements

1.

Provide a boiler installed above radiation level
with a low water cutoff device either as part of
the boiler or at the time of boiler installation.

2.

Install manual and/or automatic bleeding devices
at high points in the system to eliminate air.
Install a correctly sized expansion or
compression tank with suitable air charger and
tank drainer, as appropriate.

3.

Support the weight of all water and gas piping by
suitable hangers or floor stands.

4.

Check piping diagrams with local applicable
plumbing, heating and building safety codes.

3.2.6 Filling The System

1.

Ensure the system is fully connected. Close all
bleeding devices and open make-up water valve.
Allow system to fill slowly.

2.

If make-up water pump is employed, adjust
pressure switch on pumping system to provide a
minimum of 12 psi (81.8 kPa) at the highest
point in the heating loop.

3.

If a water pressure regulator is provided on the
make-up water line, adjust the pressure regulator
to provide at least 12 psi (81.8 kPa) at the
highest point in the heating loop.

4.

Open bleeding devices on all radiation units at
the high points in the piping throughout the
system, unless automatic air bleeders are
provided at such points.

5.

Run system circulating pump and boiler pump
for a minimum of 30 minutes with the boiler gas
shut off.

6.

Open all strainers in the circulating system,
check flow switch operation, and check for
debris.

7.

Recheck all air bleeders as described in Step 4
above.

8.

Check liquid level in expansion tank. With the
system full of water and under normal operating
pressure, the level of water in the expansion tank
should not exceed 1/4 of the total, with the
balance filled with air.

9.

Start up boiler according to procedure described
in Section 4. Operate the entire system,
including the pump, boiler, and radiation units
for one (1) hour.

10.

Recheck the water level in the expansion tank. If
the water level exceeds 1/4 of the volume of the
expansion tank, open the tank drainer and drain
to that level.

11.

Shut down the entire system and vent all
radiation units and high points in the system
piping as described in Step 4 above.

12.

Close make-up water valve and check strainer in
pressure reducing valve for sediment or debris
from the make-up water line. Reopen make-up
water valve.

13.

Check gauge for correct water pressure and also
check water level in system. If the height
indicated above the boiler insures that water is at
the highest point in the circulating loop, then the
system is ready for operation.

14.

Within three (3) days of start-up, recheck all air
bleeders and expansion tank as described in
Steps 4 and 8 above.

3.3 Water Heater (PW Model)

3.3.1 Water Chemistry

Laars equipment is designed for use in a wide

variety of water conditions. The water velocity
maintained in the heat exchanger tubes is kept high
enough to prevent scaling from hard water and low
enough to avoid corrosion from soft water. Ninety-
five percent of the urban areas in the country have
water that is compatible with this equipment, but in
some areas a water supply will contain a large
quantity of scaling chemicals or the water may be
extremely soft and corrosive. In rare situations the
water will contain both scaling chemicals and
corrosive chemicals such as calcium or sodium
chloride. These conditions may be the result of a
nearby well or pumping station and the particular
condition may not be characteristic of the entire city
water system.

If an installer observes damage from these

conditions to any water handling equipment in the
area, a factory representative should be contacted
immediately for assistance in minimizing maintenance
costs. If erosion is present, the pump impeller can be
replaced to reduce water velocity. If scaling
conditions are bad, tube cleaning maintenance
schedules can be established to prevent tube burn-out
and cracking. Neglecting the problem could mean
serious damage to the heater and water system.

Scaling can be recognized as a layer deposited

Advertising
This manual is related to the following products: