pressure should be at least 15 psi (102.2 kPa) above
the water vapor pressure corresponding to the elevated
water temperature.

Heating boilers are not suitable for open systems

unless the supply water temperatures are kept below
180°F (82°C), and a minimum of 5 psi (34.1 kPa)
static head is maintained at the boiler.

3.2.3 Hot/Chilled Water Systems

When a boiler is connected to an air

conditioning system where the same water is used for
heating and cooling, you must prevent chilled water
from entering the boiler When changing such a system
from cooling to heating, allow the chilled water to
circulate through the building, after the chiller has
been turned off, for a period long enough for the water
to warm up to at least 105°F (41°C) before the water
flows into the boiler. It is equally important to prevent
hot water from entering the chiller. The system shown
in Figure 8 is suggested to make sure the system water
is neither too hot nor too cold when a changeover
takes place. When a boiler is connected to heating
coils located in air handling units (where they may be
exposed to refrigerated air circulation), install a flow
control valve or other automatic means to prevent
gravity circulation of chilled water through the boiler.
Chilled water in the boiler will create condensate on
the boiler tubes. Boilers installed in violation of the
foregoing may void the warranty.

Figure 9. Primary-Secondary Plumbing.

Boiler Circulation

Pump

Cold Water

Make-Up

System Pump

12"

Max.

12"

Max.

12"

Max.

12"

Max.

Thermometer

Temperature
Sensor

Globe Valve

Check Valve

Pressure Reducing Valve
w/Fast Fill Bypass

Expansion Tank
with Air Scoop and
Auto Air Vent

3-Way Valve

Valve

Pump

LEGEND:

Boiler circuit piping must be equal to or larger than
boiler water connection size.

Boiler circulation pump sized for flow through
boiler.

Dotted devices indicate alternate locations.

WARNING: This drawing shows suggested
piping configuration and valving. Check with
local codes and ordinances for additional
requirements.

Purge
Valve

3-Way Valve No. 1
Change-Over
(Heating and Cooling)

3-Way Valve No. 2
To By-Pass
Both Heater and
Chiller

To
System

From
System

By-Pass

To Boiler
and
Chiller

From
Boiler

Valve Motors
2-Pos
3-Wire - 24V

115/24V
Transformer

DPDT Manual or Automatic
Change-Over Switch
DPDT - Set at Change-Over
Temperature

Clock Timer
Auto-Resetting
Set at 15 Minute SPDT

Suggested Wiring Diagram For

Tempering System Water at

Changeover From Heating To Cooling

Figure 8. Boiler-Chiller Installation.

From
Chiller

3.2.4 Combined Space Heating/Potable

Water Heating Systems

When using the Laars boiler as a source of heat

for a combined space heating/potable water heating
system, be sure to follow the instructions of the space
heating system.