LAARS HEATING SYSTEMS

Page 12

Figure 12. Connection Diagram.

Mighty-Stack
MODEL TL00

H2022200B

Table 10 lists the flow and pressure drop

requirements for the TL00-199. These values provide
the proper circulation between the water heater and a
storage tank. The pressure drop values listed include
some nominal piping:

30 feet of 1½" nominal ID copper pipe

Six - 1½" of 90° copper elbows.

Flow

Pressure

Water

Model

Water

Rate

Drop

Temp Rise

Category

GPM L/sec

ft

m

Soft

17

1.1

9

2.7

20

11

TL00-199

Normal

17

1.1

9

2.7

20

11

Hard

22

1.4

15

4.6

15

8

Table 10. Flow and Head Requirements.

*Pressure drop includes head loss of the heat

exchanger and 30 feet (9.1m) of 1½" copper pipe and
six 90° elbows.

If any of the original wire (as supplied with the appliance)
must be replaced, it must be replaced with appliance wiring
material suitable for 105 degrees C or its equivalent.