Figure 16. Troubleshooting Flowchart.

YES

NO

Turn gas supply
off. Set aquastat
to call for heat.

Is gas valve
powered? (Should
be 24V AC)

YES

NO

Does igniter warm
up and glow red?

YES

NO

Does pilot valve
open?

YES

NO

Turn gas on.
Does pilot burner
light?

YES

NO

Does main gas
valve open?

System is OK.

Check:
• On/Off toggle switch
• Line voltage/power
• Low voltage transformer
• Limit controller
• Aquastat
• Wiring
• Fan proving switch on combustion

air blower

• Roll-out switch (inside cabinet)

Unplug igniter, measure voltage at
two bottom terminals of gas valve.
Is this 24V AC?

Replace igniter.

Replace gas valve.

Replace gas valve.

Measure voltage to gas valve. Is volt-
age at least 19.5V AC?

Replace igniter.

Check transformer and
line voltage

Replace igniter sensor and save it.
Repeat the troubleshooting sequence.
Does main valve open?

Discard old igniter sensor.

NO

YES

YES

NO

YES

NO

Replace gas valve.
Re-use old igniter-sensor.