Out of production – LAARS Newport - Installation, Operation and Maintenance Instructions User Manual

Page 6

Advertising
background image

Page 6

LAARS Heating Systems

FRONT

SIDE

Figure 3. Dimensions.

7. Remove soot and scale deposits from tubes with

a flexible wire brush, taking care not to damage
“ceraform” combustion chamber, below outer
tubes.

8. Vacuum out accumulated deposits from

combustion chamber through burner port, taking
care not to damage “ceraform” combustion
chamber.

9. Replace all parts, ensuring flue-baffles are

correctly located. Ensure flue collector and
smoke-pipe are tightly sealed.

1.18 Cleaning the Chimney

Sweep all soot deposits from chimney and

smoke-pipe once a year, preferably at the end of the
heat ing season. It is also advisable to in spect the
chim ney and smoke-pipe at the be gin ning of heating
season as birds may have built their nest inside or
other material may be caus ing a blockage.

1.19 Servicing the Burner

This should only be carried out by a trained and

licensed service technician in accordance with the
burner mak er’s instructions.

1.20 Maintenance of the Tankless Coil

After several years of use, the water flow through

the coil may become restricted by mineral deposits
from the water. Mild accumulations may be removed
by an acid treatment but your servicing company can
advise on the most satisfactory method of clean ing or
whether a re place ment coil is necessary.

1.21 Coil Removal

1. Switch off electrical supply and turn off water to

boil er.

2. Valve off zones and drain boiler and DHW coil.

3. Disconnect the pipe connections to the coil.

4. Unscrew the eight retaining bolts from coil plate.

5. Pull out coil and clean or fit replacement as
necessary.

6. Ensure gasket makes a water tight seal.

7. Refill boiler, open valves and check for leaks.