Newport Oil-Fired Heater

Page 9

WARNING:- The height should not exceed 13 feet (4m)
WARNING:- The vacuum must not exceed 11.44 HG. (11.44
inches of Mercury). Burner is shipped from the factory set up
for two pipe system.
Important:- An external fi lter must be placed in the fuel line
between the fuel tank and the burner pump.

Two-Pipe
System

One-Pipe
System

Figure 5. Piping information.

Air vent

Fill pipe

Valve

Figure 5A

1¼" min.

Oil tank

"H"

Filter

"P"

Burner

Boiler

Air vent 1¼" min.

Fill pipe

Oil

tank

Figure 5B

Valve

Filter

Burner

Boiler

"H"

PIPE LENGTHS

"H"

One Pipe Gravity System

3/8" O.D.

1/2" O.D.

ft.

m

ft.

m

ft.

m

0

0

0

0

0

0

0.5

33

10.1

65

19.8

3

0.9

65

19.8

130

39.6

5

1.5

130

39.6

260

79.2

2

195

59.4

325

99

PIPE LENGTHS

"H"

Two Pipe Gravity System

3/8" O.D.

1/2" O.D.

ft.

m

ft.

m

ft.

m

0

0

0

0

0

0

0.5

115

33.0

330

100.6

3

0.9

100

30.5

330

100.6

5

1.5

80

24.4

330

100.6

2

50

15.2

295

89.9

2.9

25

7.6

100

30.5

11

3.4

20

6.1

65

19.8