SUMMIT

BOILER OR WATER HEATER

Page 13

Figure 14. Multiple Summit Water Heaters and Storage Tanks.

Hot Water Supply Piping

Follow the tank manufacturer’s guidelines for

completion of the hot water system connections.

NOTE: A listed temperature and pressure

relief valve listed as complying with the Standard
for Relief Valves and Automatic Gas Shutoff
Devices for Hot Water Supply Systems, 1). ANSI
Z21.22 latest edition, or 2). CAN / CGA 1 - 4.4, of
suitable discharge capacity must be installed in the
separate storage tank system.

4B.2 Combined Water (potable)

Heating and Space Heating
SMW-200/250 Water Heater

Piping and components connected to this water

heater for the space heating application shall be
suitable for use with potable water.

Toxic chemicals, such as used for boiler

treatment, shall not be introduced into the potable
water used for space heating.

This water heater when used to supply potable

water shall not be connected to any heating system or
component(s) previously used with a non-potable
water heating appliance.

When the system requires water for heating

at temperatures higher than required for other
uses, an anti-scald mixing or tempering valve shall
be installed to temper the water for those uses in
order to reduce scald hazard potential.

SECTION 4C.
Condensate Drain Connection

NOTE: Connecting tubing must run

DOWNWARDS from the level of the fitting (see
Figure 16).

1.

Connect a plastic tube between the plastic fitting
closer to the front of the appliance and a floor
drain (or optional condensate pump if a floor
drain is not accessible).

2.

Connect another plastic tube between the other
plastic fitting and a drain pan.

3.

The plastic tubes must not be connected
together
because the second tube is a
condensate relief tube that will function to drain
condensate if the first or primary condensate
drain tube becomes blocked.