LAARS Heating Systems

1.2 Warranty

Laars Heating Systems SUMMIT appliances are

covered by a limited warranty. The owner should fill
out the warranty registration card and return it to
Laars Heating Systems.

All warranty claims must be made to an

authorized Laars Heating Systems representative or
directly to the factory. Claims must include the serial
number and model (this information can be found on
the rating plate), installation date, and name of the
installer. Shipping costs are not included in the
warranty coverage.

Some accessory items are shipped in separate

packages. Verify receipt of all packages listed on the
packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
filed with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.

1.3 Materials Installer Must Provide

1.

Total combined feet allowed for intake and
exhaust vent pipe per instructions. The following
charts show acceptable materials for intake and
exhaust pipes:

Acceptable Intake Pipe Material

Model 200

Model 250

3-inch or 4-inch PVC

3-inch or 4-inch PVC

schedule 40 pipe per

schedule 40 pipe per

ASTM D-1785 std.

ASTM D-1785 std.

3-inch or 4-inch PVC DWV

3-inch or 4-inch PVC DWV

pipe per ASTM D-2665 std.

pipe per ASTM D-2665 std.

3-inch or 4-inch ABS-DWV

3-inch or 4-inch ABS-DWV

pipe per ASTM D2661 std.

pipe per ASTM D2661 std.

or ASTM F-628 std.

or ASTM F-628 std.

3-inch or 4-inch CPVC

3-inch or 4-inch CPVC

schedule 40 or 80 pipe per

schedule 40 or 80 pipe per

ASTM F441 std.

ASTM F441 std.

3-inch or 4-inch AL29-4C

3-inch or 4-inch AL29-4C

stainless steel complying

stainless steel complying

with UL Std. 1738

with UL Std. 1738

Acceptable Exhaust Vent Material

Model 200

Model 250

3-inch or 4-inch PVC

3-inch or 4-inch CPVC

schedule 40 pipe per

schedule 40 or 80 pipe per

ASTM D-1785 std.

ASTM F441 std.

3-inch or 4-inch PVC DWV

3-inch or 4-inch AL29-4C

pipe per ASTM D-2665 std.

stainless steel complying

with UL Std. 1738

3-inch or 4-inch ABS-DWV

pipe per ASTM D2661 std.

or ASTM F-628 std.

3-inch or 4-inch CPVC

schedule 40 or 80 ipe per

ASTM F441 std.

3-inch or 4-inch AL29-4C

stainless steel complying
with UL Std. 1738

The solvent cement for pipe joints must comply with
the following standards:

i.

PVC pipe D2564 / ABS pipe D2235, or
CPVC pipe F493

ii.

CSA listed solvent cement for the PVC,
ABS or CPVC pipe used.

2.

Electrical connection to a 120VAC/15Amp service.

3.

Gas connection that will provide 250 cubic feet/
hour at 4 to 13 inch w.c.

4.

Condensate drainage: a floor drain is preferred,
and a condensate pump can be used if required.
Check local codes for information about proper
disposal of condensate in your area.

5.

Miscellaneous copper fittings and bronze valves
will be required to complete the piping system.
Use only plastic fittings (except Nylon®) for
condensate drain lines.

1.4 Unpacking

The SUMMIT appliance is shipped in a single

crate with the following standard components on top
of the appliance.

1. Exhaust terminal

4. Hubless couplings (2)

2. Intake terminal

5. Terminal Screens, 4” (2)

3. Backing plates (4)

Figure 2. Contents of shipping package.

1.

Remove all packing and tie-down materials.

2.

Check contents of the carton against items
shown above.

1.5 Locating the SUMMIT Appliance

The appliance should be located to provide

clearances on all sides for maintenance and
inspection. It should not be located in an area where
leakage of any connections will result in damage to
the area adjacent to the appliance or to lower floors of
the structure.