LAARS SUMMIT SMB-250 - Users Manual User Manual

Page 7

Advertising
background image

SUMMIT

Page 7

Identifies

Appliance Flow Temp (Supply)

Outdoor Air Temp

Calculated Set Point

On

Off

Lock Out

Third Failure (Failure Level)

Fault Code (Three) There are 7

different Fault Codes defined.

Freeze Protection

To read or change mode

During operation display will default to supply
temperature. Press temperatures button repetitively.
To sequence through three temperature indicators.

Appliance in standby mode: will change to bFt on call
for heat.
Appliance switched OFF. Press ON/OFF button for “ON”.

After three trials for ignition, will stand in lockout. Press
reset on top of panel to retry.

To monitor, press and hold temperature button for five
seconds. Display will indicate first of eight fault memories
(FL1). Then display one of seven fault conditions that
occurred previously. Display will sequence through the
eight memories.

Sensor has detected return temperature below 39°F (4°C).

Figure 3. Typical Display Identification Codes.

Message

1H. Trouble Shooting - Fault Codes

The Summit boiler is controlled by a Pactrol

integrated boiler control (PCB) which provides seven

fault codes with eight memories. To obtain fault

messages press-in on the message center fault button

until the first fault code (FL1) is displayed. The last

recorded fault will appear e.g. F-4 (flow thermistor

faulty - open or shorted). The control will then

sequence through all eight memories, indicating

alternately the fault number and the fault code (FL1,

F-?; FL2, F=?; …, FL8, F=?). The fault number in

fault code FL1 is the most recent fault.

1H-1. Fault Code Identification
The following seven fault codes may be observed:
F-

Error corrected, control in auto reset period

(10 seconds)

F-0 No fault has occurred
F-1 Error occurred while reading fault logic of

main control

F-2 Over heat thermostat (Boiler or Flue) has

operated (open circuit)

F-3 Fan fault
F-4 Flow thermistor faulty (open or short-

circuited)

F-5 Differential Pressure Switch Contacts

opened