Complete c and deluxe d board system test, Test mode – Carrier AQUAZONE 50PTH User Manual

Page 42

Advertising
background image

42

vide cooling to the space when required. Should the capacity

be insufficient for a period greater than 5 minutes, or should a

high humidity condition occur, then the compressor will be

started to satisfy the load. Should the SAT reach the minimum

cooling SAT limit, the economizer valve will close during

compressor operation.
Heating — Additionally, the economizer control will open the

water valve should the entering water loop temperature be suit-

able for heating (at least 5 F above space temperature) and

heat is required. The valve will be controlled in a similar man-

ner except to satisfy the heating requirement. Should the coil

capacity be insufficient to satisfy the space load for more than

5 minutes, then the compressor will be started to satisfy the

load. Should the SAT reach the maximum heating SAT limit,

the economizer valve will close during compressor operation.
DEMAND LIMIT — The WSHP Open controller has the

ability to accept three levels of demand limit from the network.

In response to a demand limit, the unit will decrease its heating

set point and increase its cooling set point to widen the range in

order to immediately lower the electrical demand. The amount

of temperature adjustment in response is user adjustable for

both heating and cooling and for each demand level. The re-

sponse to a particular demand level may also be set to zero.
CONDENSER WATER LINKAGE — The control pro-

vides optimized water loop operation using an universal con-

troller (UC) open loop controller. Loop pump operation is auto-

matically controlled by WSHP equipment occupancy sched-

ules, unoccupied demand and tenant override conditions.

Positive pump status feedback prevents nuisance fault trips.

The condenser water linkage operates when a request for con-

denser water pump operation is sent from each WSHP to the

loop controller. This request is generated whenever any WSHP

is scheduled to be occupied, is starting during optimal start (for

warm-up or pull down prior to occupancy), there is an unoccu-

pied heating or cooling demand, or a tenant pushbutton over-

ride. At each WSHP, the water loop temperature and the loop

pump status is given. The WSHP will NOT start a compressor

until the loop pumps are running or will shutdown the com-

pressors should the pumps stop. This prevents the WSHP from

operating without water flow and thus tripping out on refriger-

ant pressure, causing a lockout condition. The WSHP Open

controller control will prevent this from occurring. Also, the

loop controller can be configured to start the pumps only after a

configurable number of WSHPs are requesting operation (from

1-"N"). This can be used to prevent starting the entire loop op-

eration for only one WSHP. Meanwhile, the WSHPs will not

operate if the loop pump status is off and therefore the WSHP

compressor will not run.

COMPLETE C AND DELUXE D BOARD

SYSTEM TEST

Test mode provides the ability to check the control opera-

tion in a timely manner. The control enters a 20-minute test

mode by momentarily shorting the test terminals. All time de-

lays are sped up 15 times. The following operations are com-

mon to both Complete C and Deluxe D controls.

Test Mode —

To enter Test mode, cycle the fan 3 times

within 60 seconds. The LED will flash a code representing the

last fault when entering the Test mode. The alarm relay will

also power on and off during Test mode. See Tables 27 and 28.

To exit Test mode, short the terminals for 3 seconds or cycle

the fan 3 times within 60 seconds.
NOTE: The flashing code and alarm relay cycling code will

both have the same numerical label. For example, flashing

code 1 will have an alarm relay cycling code 1. Code 1 indi-

cates the control has not faulted since the last power off to

power on sequence.

Table 27 — Complete C Control Current LED

Status and Alarm Relay Operations

LEGEND

NOTES:

1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by

a 10-second pause. This sequence will repeat continually until the fault is
cleared.

Table 28 — Complete C Control LED Code and

Fault Descriptions

LEGEND

LED STATUS

DESCRIPTION OF OPERATION

ALARM RELAY

On

Normal Mode

Open

Normal Mode with

PM Warning

Cycle

(closed 5 sec.,

open 25 sec.)

Off

Complete C Control is

non-functional

Open

Slow Flash

Fault Retry

Open

Fast Flash

Lockout

Closed

Slow Flash

Over/Under Voltage Shutdown

Open,

(Closed after

15 minutes)

Flashing Code 1

Test Mode — No fault in memory

Cycling Code 1

Flashing Code 2

Test Mode —

HP Fault in memory

Cycling Code 2

Flashing Code 3

Test Mode —

LP Fault in memory

Cycling Code 3

Flashing Code 4

Test Mode —

FP1 Fault in memory

Cycling Code 4

Flashing Code 5

Test Mode —

FP2 Fault in memory

Cycling Code 5

Flashing Code 6

Test Mode —

CO Fault in memory

Cycling Code 6

Flashing Code 7

Test Mode — Over/Under

shutdown in memory

Cycling Code 7

Flashing Code 8

Test Mode — PM in memory

Cycling Code 8

Flashing Code 9

Test Mode — FP1/FP2

Swapped Fault in memory

Cycling Code 9

CO

Condensate Overflow

FP

Freeze Protection

HP

High Pressure

LED

Light-Emitting Diode

LP

Low Pressure

PM

Performance Monitor

LED

CODE

FAULT

DESCRIPTION

1

No fault in memory

There has been no fault since
the last power-down to power-
up sequence

2

High-Pressure Switch

HP switch opens instantly

3

Low-Pressure Switch

LP switch opens for
30 continuous seconds before
or during a call (bypassed for
first 60 seconds)

4

Freeze Protection Coax
— FP1

FP1 below Temp limit for
30 continuous seconds
(bypassed for first 60 seconds of
operation)

5

Freeze Protection Air Coil —
FP2

FP2 below Temp limit for
30 continuous seconds
(bypassed for first 60 seconds of
operation)

6

Condensate overflow

Sense overflow (grounded) for
30 continuous seconds

7

(Autoreset)

Over/Under Voltage
Shutdown

"R" power supply is <19VAC or
>30VAC

8

PM Warning

Performance Monitor Warning
has occurred.

9

FP1 and FP2
Thermistors are swapped

FP1 temperature is higher than
FP2 in heating/test mode, or
FP2 temperature is higher than
FP1 in cooling/test mode.

FP

Freeze Protection

HP

High Pressure

LED

Light-Emitting Diode

LP

Low Pressure

PM

Performance Monitor

Advertising
This manual is related to the following products: