Wshp open controller, Thermostatic expansion valves, Caution – Carrier AQUAZONE 50PTH User Manual

Page 46

Advertising
background image

46

WSHP Open Controller —

With the WSHP Open con-

troller option, the 100 most recent alarms can be viewed using

the BACview

6

alarm status and alarm history.

To view the alarms:

1. Navigate to the Alarm Status screen from the Home

screen using the arrow softkeys. The screen will display

the current alarm status, either normal or Alarm, and al-

low for scrolling through the unit’s alarm status.

2. From the Alarm Status screen, press the Alarm softkey to

view the 100 most recent alarms which are labeled with

date and time for easy reference.
NOTE: Active faults can be viewed by scrolling down,

these faults indicate a possible bad sensor or some condi-

tion which may not merit an alarm.

3. To view alarms which have been corrected, scroll down

through the Alarm screen to Return Top Normal screen.
NOTE: Alarms are automatically reset once alarm con-

dition has been corrected.
See Table 32 for possible alarm cause and solution.

Thermostatic Expansion Valves —

Thermostat-

ic expansion valves (TXV) are used as a means of metering the

refrigerant through the evaporator to achieve a preset superheat

at the TXV sensing bulb. Correct superheat of the refrigerant is

important for the most efficient operation of the unit and for the

life of the compressor.

Packaged heat pumps typically use one bi-flow TXV to me-

ter refrigerant in both modes of operation. When diagnosing

possible TXV problems it may be helpful to reverse the refrig-

erant flow to assist with the diagnosis.

Geothermal and water source heat pumps are designed to

operate through a wide range of entering-water temperatures

that will have a direct effect on the unit refrigerant oper-

ating pressures. Therefore, diagnosing TXV problems can be

difficult.
TXV FAILURE — The most common failure mode of a TXV

is when the valve fails while closed. Typically, a TXV uses

spring pressure to close the valve and an opposing pressure,

usually from a diaphragm, to open the valve. The amount of

pressure exerted by the diaphragm will vary, depending on the

pressure inside of the sensing bulb. As the temperature of and

pressure within the bulb decreases, the valve will modulate

closed and restrict the refrigerant flow through the valve. The

result is less refrigerant in the evaporator and an increase in the

superheat. As the temperature at the bulb increases the dia-

phragm pressure will increase, which opens the valve and

allows more refrigerant flow and a reduction in the superheat.

If the sensing bulb, connecting capillary, or diaphragm

assembly are damaged, pressure is lost and the spring will force

the valve to a closed position. Often, the TXV will not close

completely so some refrigerant flow will remain, even if inade-

quate flow for the heat pump to operate.

The TXV sensing bulb must be properly located, secured,

and insulated as it will attempt to control the temperature of the

line to which it is connected. The sensing bulb must be located

on a dedicated suction line close to the compressor. On a pack-

aged heat pump, the bulb may be located almost any place on

the tube running from the compressor suction inlet to the

reversing valve. If the bulb is located on a horizontal section, it

should be placed in the 10:00 or 2:00 position for optimal

performance.

0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

90.0

0.0

20.0

40.0

60.0

80.0

100.0

120.0

140.0

Temperature (degF)

Resistance (kOhm)

Fig. 37 — Thermistor Nominal Resistance

CAUTION

Use caution when tightening the strap. The strap must be

tight enough to hold the bulb securely but caution must be

taken not to over-tighten the strap, which could dent, bend,

collapse or otherwise damage the bulb.

SUCTION

COMPRESSOR

DISCHARGE

COAX

EXPANSION

VALVE

FP2

FP1

LIQUID
LINE

WATER IN

WATER OUT

CONDENSATE

OVERFLOW

(CO)

AIR COIL
FREEZE
PROTECTION

WATER
COIL
PROTECTION

THERMISTOR

(

°F)

(

°F)

AIR

COIL

AIRFLOW

AIRFLOW

LEGEND

Fig. 38 — FP1 and FP2 Thermistor Location

COAX

Coaxial Heat Exchanger

Airflow

Refrigerant Liquid Line Flow

Advertising
This manual is related to the following products: