NORAC UC4.5-BC Operator Manual User Manual

Page 28

Advertising
background image


24

Automatic Dead Zone Calibration:

Follow Section 8.1.1 (level booms, working RPM, etc.) before proceeding.

Ensure the UC4.5 control panel is in manual mode, at the run screen.

Navigate to the "More?" menu prompt in the SETUP (

) menu. Press

to confirm.

Navigate to the boom section to be set up, for example "Left?" to adjust the left up or the
left down settings. Press the

button to confirm.

Press the

button to access the next menu prompt. Choose the dead zone up or down

setting (Figure 10).

Press and hold the

button.

When the "Done" message is displayed, release the

button to view the new setting.

Manual Dead Zone Calibration:

Follow Section 8.1.1 (level booms, working RPM, etc.) before proceeding.

Ensure the UC4.5 control panel is in manual mode, at the run screen.

Navigate to the "More?" menu prompt in the SETUP (

) menu. Press

to confirm.

Navigate to the boom section to be setup, for example, "Left?" to adjust the left up and/or
the left down settings. Press the

button to confirm.

Press the

button to access the next menu prompt. Choose the dead zone up or down

setting (Figure 10).

Press and hold the

button.

The valve will turn on at the indicated setting for exactly one second. The screen will show
the actual change in height.

The change in height reading is live as long as the

button is held. Wait until the height

reading has settled to a stable value and record this reading.

Average three readings. The acceptable average change in height should be from 0.5 to 1.5
inches (13 to 38 mm). Ideal would be 1 inch exactly (25 mm).

If the average is less, increase the DZ setting with the

button. If the average is more,

decrease the DZ setting with the

button.

Repeat the manual dead zone test until the average falls into the acceptable range.