Table 5 — Electrical Data, Alternate Motors

UNIT

V*-PH-HZ

VOLTAGE

LIMITS

FAN MOTOR

POWER SUPPLY

Hp

FLA

Minimum

Circuit Amps

MOCP

40RM

007

208/230-1-60

187-253

2.4

11.0

13.8

20

208/230-3-60

187-253

2.9

7.5

9.4

15

460-3-60

414-528

2.9

3.4

4.3

15

575-3-60

518-632

2.0

2.4

3.0

15

40RM

40RMQ

40RMS

008

208/230-3-60

187-253

2.9

7.5

9.4

15

460-3-60

414-528

2.9

3.4

4.3

15

575-3-60

518-632

3.0

3.8

4.8

15

230-3-50

207-253

2.9

7.5

9.4

15

400-3-50

360-440

2.9

3.4

4.3

15

40RMS

010

208/230-3-60

187-253

2.9

7.5

9.4

15

460-3-60

414-528

2.9

3.4

4.3

15

575-3-60

518-632

3.0

3.8

4.8

15

230-3-50

207-253

2.9

7.5

9.4

15

400-3-50

360-440

2.9

3.4

4.3

15

40RM

40RMQ

40RMS

012

208/230-3-60

187-253

3.7

10.6

13.3

20

460-3-60

414-528

3.7

4.8

6.0

15

575-3-60

518-632

3.0

3.8

4.8

15

230-3-50

207-253

5.0

14.4

18.0

30

400-3-50

360-440

5.0

7.2

9.0

15

40RM

40RMS

014

208/230-3-60

187-253

3.7

10.6

13.3

20

460-3-60

414-528

3.7

4.8

6.0

15

575-3-60

518-632

5.0

5.6

7.0

15

230-3-50

207-253

5.0

14.4

18.0

30

400-3-50

360-440

5.0

7.2

9.0

15

40RM

40RMQ

40RMS

016

208/230-3-60

187-253

5.0

15.2/14.4

19.9/18.0

30/30

460-3-60

414-528

5.0

7.2

9.0

15

575-3-60

518-632

5.0

5.6

7.0

15

230-3-50

207-253

5.0

14.4

18.0

30

400-3-50

360-440

5.0

7.2

9.0

15

40RM

40RMS

024

208/230-3-60

187-253

7.5

22.0/21.0

27.5/26.3

45/45

460-3-60

414-528

7.5

10.5

13.1

20

575-3-60

518-632

7.5

7.6

9.5

15

230-3-50

207-253

7.5

21.0

26.3

45

400-3-50

360-440

7.5

10.5

13.1

20

40RM

40RMS

028

208/230-3-60

187-253

10.0

26.4/25.0

33.0/31.3

55/55

460-3-60

414-528

10.0

12.5

15.6

25

575-3-60

518-632

10.0

9.6

12.0

20

230-3-50

207-253

10.0

25.0

31.3

55

400-3-50

360-440

10.0

12.5

15.6

25

LEGEND

FLA

Full Load Amps

MOCP — Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nomi-

nal voltages shown. Voltages should not exceed the limits shown in
the Voltage Limits column.

NOTES:
1. Minimum Circuit Amp and MOCP values are calculated in

accordance with NEC (National Electrical Code) (U.S.A. stand-
ard), Article 440.

2. Motor FLA values are established in accordance with UL (Under-

writers’ Laboratories) Standard 1995 (U.S.A. standard).

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 400-3-50.

AB = 393 v
BC = 403 v
AC = 396 v

393 + 403 + 396

Average Voltage =

3

1192

=

3

= 397

Determine maximum deviation from average voltage.

(AB) 397 − 393 = 4 v
(BC) 403 − 397 = 6 v
(AC) 397 − 396 = 1 v

Maximum deviation is 6 v.

Determine percent voltage imbalance.

6

% Voltage Imbalance = 100 x

397

= 1.5%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

21