Carrier 40RMQ User Manual

Page 36

Advertising
background image

Legend and Notes for Table 10A and 10B

LEGEND

Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure

NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and

034; 1200 rpm for all other sizes.

2. Fan performance is based on deductions for wet coil, clean 2-in.

filters, and unit casing. See right for factory-supplied filter pres-
sure drop.

3. Refer to fan motor and drive tables for additional data.

Factory-Supplied Filter Pressure Drop — English

UNIT

AIRFLOW

(Cfm)

PRESSURE DROP

(in. wg)

40RM

007

1,800
2,400
3,000

0.05
0.08

0.11

40RM

40RMQ

40RMS

008

2,250
3,000
3,750

0.07

0.11

0.15

40RMS

010

2,550
3,400
4,250

0.09
0.13
0.18

40RM

40RMQ

40RMS

012

3,000
4,000
5,000

0.11

0.17
0.23

40RM

40RMS

014

3,750
5,000
6,250

0.06
0.10
0.13

40RM

40RMQ

40RMS

016

4,500
6,000
7,500

0.08
0.12
0.17

40RM

40RMS

024

6,000
8,000

10,000

0.12
0.19
0.26

40RM

40RMS

028

7,500

10,000
12,500

0.15
0.22
0.30

40RM

40RMS

034

9,000

12,000
15,000

0.19
0.29
0.40

36