Roof curb dimensions for model rpbl, Ac d – Reznor RPBL Unit Installation Manual User Manual

Page 11

Advertising
background image

Form I-SSCBL/RPBL, P/N 149159 R7, Page 11

Roof Curb Dimensions for Model RPBL

Size

400

500/600

700

800

1050

1200

Option CJ1 - Roof Curb for RPBL

A

inches

82-1/4

108-1/4

108-1/4

108-1/4

134-1/4

134-1/4

mm

2089

2750

2750

2750

3410

3410

B

inches

54-1/2

43-9/16

49-1/16

54-1/2

49-1/16

54-1/2

mm

1384

1106

1246

1384

1246

1384

C*

inches

78-1/2

104-1/2

104-1/2

104-1/2

130-1/2

130-1/2

mm

1994

2654

2654

2654

3315

3315

D*

inches

50-13/16 39-13/16 45-5/16 50-13/16 45-5/16 50-13/16

mm

1291

1011

1151

1291

1151

1291

Wt

lbs

150

167

173

179

202

208

kg

68

76

78

81

92

94

Option CJ2 - Roof Curb for RPBL with Factory-Installed

Downturn Plenum, Option AQ5 or AQ8

A

inches

106-1/4

132-1/4

132-1/4

132-1/4

158-1/4

158-1/4

mm

2699

3359

3359

3359

4020

4020

B

inches

54-1/2

43-9/16

49-1/16

54-1/2

49-1/16

54-1/2

mm

1384

1106

1246

1384

1246

1384

C*

inches

102-1/2

128-1/2

128-1/2

128-1/2

154-1/2

154-1/2

mm

2604

3264

3264

3264

3924

3924

D*

inches

50-13/16 39-13/16 45-5/16 50-13/16 45-5/16 50-13/16

mm

1291

1011

1151

1291

1151

1291

Wt

lbs

177

193

199

205

228

234

kg

80

88

91

93

103

106

Size

400

500/600

700

800

1050

1200

Option CJ4 - Roof Curb for RPBL with Field-Installed** Cooling

Coil Cabinet, Option AU2 or AU3

A

inches

150-1/4

165-1/4

170-3/4

176-1/4

1 -3/4

202-1/4

mm

3816

4197

4337

4477

4997

5137

B

inches

54-1/2

43-9/16

49-1/16

54-1/2

49-1/16

54-1/2

mm

1384

1106

1246

1384

1246

1384

C*

inches

146-1/2

161-1/2

167

172-1/2

193

198-1/2

mm

3721

4102

4242

4382

4902

5042

D*

inches

50-13/16 39-13/16 45-5/16 50-13/16 45-5/16 50-13/16

mm

1291

1011

1151

1291

1151

1291

Wt

lbs

227

231

243

255

271

282

kg

103

105

110

116

123

128

Option CJ5 - Roof Curb for RPBL with Field-Installed** Cooling

Coil Cabinet w/Downturn, Option AU11, AU12, AU13 or AU14

A

inches

174-1/4

189-1/4

194-3/4

200-1/4

220-3/4

226-1/4

mm

4426

4807

4947

5086

5607

5747

B

inches

54-1/2

43-9/16

49-1/16

54-1/2

49-1/16

54-1/2

mm

1384

1106

1246

1384

1246

1384

C*

inches

170-1/2

185-1/2

191

196-1/2

217

222-1/2

mm

4331

4712

4851

4991

5512

5652

D*

inches

50-13/16 39-13/16 45-5/16 50-13/16 45-5/16 50-13/16

mm

1291

1011

1151

1291

1151

1291

Wt

lbs

253

257

269

280

296

308

kg

115

117

122

127

134

140

*

C and D are roof opening dimensions.

** Field installed means that the cooling coil cabinet with or without the downturn is factory assembled and shipped

separately. The roof curb is sized to accommodate the complete length of the system. The shipped-separate cooling

coil cabinet with or without a downturn must be lifted to the roof separately from the packaged system, set on the roof

curb, and attached to the furnace section (see instructions in Paragraph 6.3.6).

*Optional

Downturn Plenum

Furnace

Blower

Cabinet

Curb

Cap

1-7/8”

(48mm)

Roof

Curb

16” (406mm)

1-7/8”

(48mm)

AC

D

Return

Duct

Supply

Duct

1-7/8”(48mm)

1-1/2”

(38mm)

Lift Holes

(4 corners)

B

FIGURE 9A - Optional Roof

Curb and Dimensions for

Model RPBL

IMPORTANT: Top surface of the

roof curb MUST be sealed.

* Illustration is shown with an Option AQ5 or AQ8

downturn plenum. The system can have a variety

of configurations which affect installation.

• If the system does not have a downturn plenum,

the discharge is horizontal.

• Downturn plenum Options AQ5 and AQ8 are

factory installed to be lifted to the roof and set on

the roof curb as part of the packaged system.

• If the system has an Option AU2 or AU3 cooling

coil cabinet, the discharge is horizontal. If

the system has an AU11, AU12, AU13, AU14

cooling coil cabinet, there is a downturn plenum

with vertical discharge.

Options AU2, AU3,

AU11, AU12, AU13, and AU14 are not factory

installed. Options AU2, AU3, AU11, AU12,

AU13, and AU14 must be lifted to the roof

separately from the packaged system, set on

the roof curb, and attached to the furnace.

IMPORTANT: Area enclosed by the roof curb must comply with clearance to

combustible materials. If roof is constructed of combustible materials, area

within curb must be either ventilated, left open, or covered with non-combus-

tible material which has an "R" value of at least 5.0. If area within curb is left

open, higher radiated sound levels may result.

Bottom Duct Connections - The blower section and optional downturn plenum have

duct flanges for connection to return air and supply air ducts. Duct opening sizes and

curb spacing shown in

FIGURE 9D are for currently manufactured curbs that are avail-

able from the system manufacturer.