2 start-up, 3 check installation after start-up – Reznor RPBL Unit Installation Manual User Manual

Page 53

Advertising
background image

Form I-SSCBL/RPBL, P/N 149159 R7, Page 53

9.2 Start-Up

Close all panels tightly. Turn electric and gas supply on to the furnace. Adjust

the thermostat or ductstat so that a call for heat exists. Observe for complete

sequencing of safety pilot and ignition.

Operating Sequence

1. Set the thermostat switch at its lowest setting.

2. Turn on power.

3. Turn on the manual gas valves.

4. Set thermostat at desired setting.

5. Thermostat calls for heat

a) The venter motor is energized after 15-second

(approximate) time delay.

b) Venter flow switches from N.C. to N. O. contacts,

energizing the pilot gas valve and spark gap

to produce a pilot flame on each operating

cycle. The sensing probe proves the presence

of the pilot flame and energizes the safety

switch portion of the control. The switch action

de-energizes the spark gap and energizes the

main valve. The main gas ignites and the unit

fires at full rate.

c) If the flame is extinguished during main burner

operation, the safety switch closes the main valve

and recycles the spark gap. On a unit equipped

with a controller with lockout, if the pilot is not

established within 120 seconds (approximately),

the unit locks out for one hour, unless reset by

interrupting the power to the control circuit (See

Lighting Instructions).

6. Blower motor operates from fan time delay.
7. Thermostat is satisfied.

a) Solenoid gas valve de-energized.

b) Pilot gas valve de-energized.

c) Ignition controller de-energized.

d) Time delay relay keeps venter motor on for

approximately 90 seconds (post purge).

8. To shut down, set thermostat to lowest setting.

Blower motor remains on as determined by fan time

delay.

9.3 Check

installation after

Start-up:

Observe burner flame at full fire. Natural gas flame should be about 1-1/2" in height

with blue coloring. Propane gas flame should be approximately the same length

with blue coloring. Yellow tipping may appear on propane gas. If yellow extends

beyond 1/2 to 3/4", adjust air shutters. See Paragraph 8.11. If shutter adjustment

will not reduce yellowing, check for gas leaks at the control manifold or orifice

fitting.

Turn the unit off and on, pausing two minutes between each cycle. Observe

for smooth ignition. On two-stage or modulating burner systems, manipulate

temperature adjustment slowly up and down to see if control is sequencing or

modulating properly. Raising temperature setting drives burner on or to full fire.

Using a manometer or slant gauge readable up to 14" w.c., check orifice manifold

for operating pressure on full fire. Natural gas should be 3.5" w.c. at this point.

Propane gas should be 10" w.c. at this point. Variations from these pressures

are not recommended, as ignition and efficiency performance can be adversely

affected by improper pressure adjustment. See Paragraph 6.1.

With optional dirty filter switch - Set switch. See Paragraph 6.3.4.

Place "Owner's Envelope" containing Limited Warranty Card, this booklet, and

any optional information in an accessible location near the heater. Follow the

instructions on the envelope.

DANGER

The gas burner in this gas-fired equipment is designed and equipped to provide safe, complete

combustion. However, if the installation does not permit the burner to receive the proper supply of

combustion air, complete combustion may not occur. The result is incomplete combustion which

produces carbon monoxide, a poisonous gas that can cause death. Safe operation of separated-

combustion, indirect-fired gas burning equipment requires a sealed, properly operating vent system

which vents all flue products to the outside atmosphere. FAILURE TO PROVIDE PROPER VENTING

WILL RESULT IN A HEALTH HAZARD WHICH COULD CAUSE SERIOUS PERSONAL INJURY OR

DEATH.
Install either the horizontal or vertical combustion air/vent system illustrated in Paragraph 6.2

using the concentric adapter supplied. Always comply with the combustion air requirements in

the installation codes and instructions. Combustion air at the burner should be regulated only

by manufacturer-provided equipment. NEVER RESTRICT OR OTHERWISE ALTER THE SUPPLY

OF COMBUSTION AIR TO ANY HEATER. CHECK THE COMBUSTION AIR/VENT SYSTEM FOR

SOUNDNESS AND FUNCTION; MAINTAIN IT IN PROPER OPERATING CONDITION.

Advertising
This manual is related to the following products: