Form I-Y, P/N 273646R6, Page 74

Start-Up Information Form

Applies to:

Models YDHA, YDMA, and YDSA

STARTUP FORM

Job Name

Contractor

Verify shipping brackets are removed.

Inspect unit for damage.

Check clearances.
Seal electrical entrances.

Startup Check List - General Checks

Street
City, ST, Zip

Date

Contact
Model
Serial No.

Phone

Size

Tag

Check coil condensate drain and trap.

FLA-1

Makeup air control (Option D21) - field-installed sensor.
Space Control (Option D19) - field-installed sensor and

thermostat.

Dirty filter switch(es) - factory installed / setting required.

Convenience outlet - 115v supply required.

Low ambient phase control

Low ambient modulating control

DDC Phase loss (factory installed).

Firestat (field-installed/manual reset).

Smoke detector (field installed).

Disconnect Switch (required) - factory or field installed.

Inspect optional dampers.

Verify outside air hood is installed.

Check condenser fans for free movement.

L1 - L2

DP*

CFM

L2 - L3

L3 - L1

Verify all copper tubing is isolated and does not rub.

Check discharge and space sensors.

Verify inlet air filters are installed.

Check and tighten all electrical terminals.

Check fuses/breakers/disconnects for correct sizing

(Check unit rating plate for requirements.)

Check

Rotation.

Set supply fan CFM using Test Mode.

Constant Volume

Building Pressure

(field-installed tubing

and pressure ports)

Duct Pressure

(field-installed

sensor and tubing)

Supply Fan Tracking

Building Pressure

(field-installed tubing

and pressure ports)

Constant Volume

Set optional exhaust fan CFM using Test Mode.

Circuit
Compressor A
Compressor B
D or Reheat DH

NOTE: Crankcase heaters must be allowed to warm up for at least 24 hours prior to startup.

Supply Fan - Cooling
Supply Fan - Optional

Heating (Gas or Electric)
Optional Exhaust Fan

Supply Fan Control

Optional Exhaust

Fan Control

Voltage (at the contactors)

Supply Fan and Optional Exhaust Fan

Check optional hot gas bypass valve setting.

Compressors

Outdoor Air Conditions:

Entering Dry Bulb

Entering Wet Bulb, Dewpoint, or % RH

FLA-3

FLA-2

L3 - L1

L2 - L3

L1 - L2

Nameplate

RLA

Head

Pressure

PSIG

Suction

Pressure

PSIG

Superheat

DAT

Subcooling

Amperage

Voltage (at the contactors)

Condenser Fans

Optional Condenser Fan Control

Nameplate HP

Volts

FLA

Fan 1
Fan 2

Fan 3

L2 - L3

L3 - L1

FLA-1

FLA-2

Fan 4

FLA-3

L1 - L2

Voltage (at the contactors)

Amperage

* Inlet Ring Differential Static Pressure

Check for voltage imbalance.

Check for manual resets (DX high pressure switch;

optional firestat, optional high gas pressure switch)

Option Check List

Purge air from lines

Natural Gas

High Altitude

Propane

Sea Level

Staged
Modulating

(SCR)

Leak test all piping

Inlet Gas Pressure

Optional Gas Heat Section

Measure Manifold Pressure

Condensate Drain(s)

and Trap
Vent

Optional Heat Tape

Optional Condensate

Pump

Optional Neutralizer

Kit

Optional

Electric

Heat

Section

Electric Heat

Control

Optional Electric Pre-Heat

L3 - L1

Voltage (at the contactors)

Amperage

L1 - L2

FLA-3

Voltage

Amperage

L1 - L2 L2 - L3

Low

High

Heat Section 2

Heat Section 1

Low

High

L3 - L1 FLA-1 FLA-2 FLA-3

FLA-2

FLA-1

4

Optional

Energy

Recovery

Wheel

Belt tension

10kw

20kw

30kw

Rotation and

Alignment

L2 - L3

1

3

2

©2013 Thomas & Betts; All rights reserved

Modulating Control

Staged Control

High Efficiency

Heat Section

Heat Section 1

Heat Section 2

Print Form

Reset Form