0 clearances and dimensions (cont’d), 2 dimensions (cont’d), Figure 3 - cabinet size 2 dimensions - inches (mm) – Reznor YDSA Unit Installation Manual User Manual

Page 8

Advertising
background image

Form I-Y, P/N 273646R6, Page 8

Optional

Outside

Air Hood

Airflow

Hood

66-1/2

(1689)

B - Inside the Curb Cap

A - Base Length

51-11/16 (1313)

- Inside the Curb Cap

Top

View

Side View

Inlet Air End Views

Utility Entrance Dimensions

Bottom View showing Duct Openings

Supply Air Discharge

Return Air

Inlet

Outside

Air Inlet

(4) Corner Lifting

Points - 1-1/2 (38mm)

88-1/8 (2238)

- Base Width

Power

Exhaust

Box with

Optional

Wheel

1-1/4” Ø Condensate

Drain Connection

Optional

Wheel Access Damper Access

Coil &

Filter

Access

Fan

Access

Optional

Heat Section

Control Access

Condenser

Section

5-7/8 (149)

X

Power Exhaust

Box with

Optional Wheel

Condenser

Section

40-5/16

(1024)

5-1/8

(130)

w/std

gas

heat

only

89-15/16

(2284)

58-5/8

(1489)

31-5/16

(795)

65-9/16

(1665)

C

24

(610)

D

**Optional

Disconnect

Switch

**Power

Supply

Gas

Inlet

31-7/16

(799)

30

(762)

18

(457)

6-1/8 (155)

6-1/8

(155)

45

(1143)

45

(1143)

6 (152)

8 (203)

6-1/4 (159)

5-1/4

(133)

57-11/16

(1468)

49-11/16

(1264)

14 (356)

24-9/16

(624)

Optional

Exhaust

Dampers

without

an energy

recovery

wheel

Vent Outlet - Standard (non-condensing)

Gas Heat Section

Control Access

Vent

Outlet

(gas

heat)

X

Y

Z

Y

*Vent Outlets -

High Efficiency

(condensing)

Gas Heat Section

Optional Gas

Heat Section

Control End View with High

Efficiency Gas Heat Section

(See dimensions below.)

Control End View with Electric or

Non-Condensing Gas Heat Section

* High-efficiency dual heat sections have two vent outlets.

** Two power supply entrances and two disconnect switches apply

only to systems with dual disconnect Option BA7.

Models and Cooling Sizes

Cabinet

Size

System without Energy Recovery

Wheel

System with Optional Energy

Recovery Wheel

A1

B1

C1

D1

A2

B2

C2

D2

Dimensions - inches

Dimensions - inches

YDMA & YDHA 180, 210, 240

and YDSA 120, 150

2

132-17/32 124-21/32 131-19/32 24-7/16 140-27/32

133 139-31/32 32-25/32

Dimensions - mm

Dimensions - mm

YDMA & YDHA 180, 210, 240

and YDSA 120, 150

2

3366

3167

3342

621

3577

3378

3555

833

4.2 Dimensions (cont’d)

FIGURE 3 - Cabinet Size 2 Dimensions - inches (mm)

Important NOTE: DO NOT use base dimensions for roof curb. See Paragraph 5.3.

Opening Dimensions

inches (mm)

Supply Air

Discharge

45 x 30

(1143) x (762)

Return Air

Inlet

45 x 18

(1143) x (457)

Outside Air Inlet - Sizes by Option:
Option

X

Y

Z

AR1

49-5/8

(1260)

25-5/8

(651)

5-1/2

(140)

AR7

45-3/4

(1162)

8

(203)

7

(178)

AR25, AR2G,

AR2H & all

models with

Wheel option

49-5/8

(1260)

25-5/8

(651)

5-1/2

(140)

Gas Connection Location and Size for Systems with Optional Gas Heat Section

Gas Heat Section (H=non-condensing; G=condensing heat section)

X

Y

Diameter

(NPT)

Single Furnace

Dual Furnaces (one gas connection)

H75, H100

H125, H150, H175, H202

10-15/16”

(278 mm)

13-11/16”

(348 mm)

1/2”

H200, G150

H402, G302

7-11/16”

(195 mm)

14-1/8”

(359 mm)

1/2”

H300, H400, G225, G300

G372

3/4”

4.0 Clearances and Dimensions (cont’d)

Advertising
This manual is related to the following products: