Form O-CAUA, P/N 164772 R7, Page 13

Modulating

Damper Motor,

P/N 196302 with

Logic Module

Modulating Damper Motor with Logic Module

Function: The modulating damper motor actuates the dampers in

response to enthalpy controls for cooling or a mixed air controller for

heating. Outside air dampers close when the heater shuts down.

Service: There is no service required other than external cleaning. If

the motor or module needs replaced, replace with identical parts.

Potentiometer

Potentiometer

Function: The potentiometer is a manually set switch used with modulating dampers

to set a minimum outside air damper opening. It is either mounted in the mixing box or

remotely located.

Service: If the potentiometer needs replaced, replace it with an identical switch.

Return Air Controller

Function: The return air controller senses the temperature of the incoming return

air. On a two-position outside air damper system, it activates the motor to open and

close the outside air damper. On a modulating system, the return air controller main-

tains 100% return air until the set temperature is reached at which point the mixed air

controller (with or without potentiometer) controls the dampers based on the mixed air

control setting. When in the heating mode, the temperature of the "mixed" return and

outside air entering a standard Model CAUA heater must always be 35°F or above.

Only when the heater is factory equipped with makeup air Option AD4 can the entering

air temperature be below 35°F.

Service: If the controller needs replaced, replace it with an identical control.

Mixed Air Controller

Function: The mixed air controller senses the temperature of the air entering the

heater. It automatically operates the damper motor to modulate the outside and return

air dampers based on the temperature setting. When in the heating mode, the tem-

perature of the "mixed" return and outside air entering a standard Model CAUA heater

must always be 35°F or above. Only when the heater is factory equipped with makeup

air Option AD4 can the entering air temperature be below 35°F.

Service: If the controller does not function properly, replace it with an identical control.

Return Air

Controller

Mixed Air

Controller

2-Position

Enthalpy

Control

Modulating Enthalpy

Sensor and Thermistor

Sensor

Enthalpy Sensor for 2-Position Control

Function: The enthalpy control senses the enthalpy (heat content in a lb of air) of

the outside air entering the heater. When the enthalpy is low, the control activates the

motor to open the outside air damper; when high, it closes the outside air damper.

Service: If the controller does not function properly, replace it with an identical control.

Enthalpy Sensors for Modulating Control

Function: There are two enthalpy sensors, one for outside air and one for return air.

Input from the two enthalpy sensors and the thermistor sensor to the logic module on

the motor allow the motor to modulate the dampers to maintain the set temperature

and control the moisture of the air entering the heater.

Service: If the controls do not function properly, replace with an identical control.

TABLE 5 - Application

of Inlet Air Damper

Controls by Option

Codes (page 14)

IMPORTANT NOTE: The standard Model CAUA is designed for a maximum tempera-

ture rise of 75°F. Above 35°F (2°C) outside air temperature, any percentage of outside

air is permitted. For optimum operation and to prevent condensation, the mixed air

temperature going to the heat exchanger must not be below 35°F (2°C).
The inlet air temperature restriction does not apply to a Model CAUA ordered with

makeup air Option AD4. A CAUA unit equipped with makeup air Option AD4 includes

stainless steel components and a flue wrapper condensate drain to permit inlet air

temperature below 35°F (2°C).