Hardware hookup, Crestron csp-lsp lightning strike protector – Crestron electronic CSP-LSP User Manual

Page 17

Advertising
background image

Crestron CSP-LSP

Lightning Strike Protector

Hardware Hookup

The CSP-LSP can be connected locally to protect a nearby control
system and Cresnet devices. The CSP-LSP can also be connected to
remote Cresnet devices or another CSP-LSP to provide protection to
Cresnet devices that are connected with substantially longer wire runs.
Make the necessary connections as called out in the illustrations below
and on the next page. Refer to “Network Wiring” on page 11 when
attaching the 4-position terminal block connectors. Be sure to carefully
review each hardware connection diagram before proceeding.

Local
Connections

Local connections refer to connections made from the CSP-LSP to Cresnet
devices which do not include wire runs exceeding 500 feet or wire runs
situated outdoors, including underground wire runs. Cresnet devices at these
local distance are referred to as local Cresnet devices.

Local Hardware Connections for the CSP-LSP

CRESNET*:

CONNECT TO ANY

CRESNET DEVICE

CRESNET:

CONNECT TO

CONTROL SYSTEM,

C2N-HBLOCK, OR

ANY LOCAL

CRESNET DEVICE

THAT IS TO BE

PROTECTED

DAISY CHAIN TO SECOND CSP-LSP USING

PROVIDED GROUND BUS BAR

GROUND:

CONNECT TO GOOD EARTH GROUND USING PROVIDED BRAIDED

GROUND STRAP. SECURE END OF GROUNDING STRAP BETWEEN

TWO KEP NUTS ONTO THE GROUNDING STUD.

* When making a connection to a remote Cresnet device or remote CSP-LSP, only
connect the data and ground wires.

Operations & Installation Guide – DOC. 6643A

Lightning Strike Protector: CSP-LSP

13