SilentKnight 5808 User Manual

Page 26

Advertising
background image

IntelliKnight 5808 Installation Manual

151274-L8

3-9

SD500-LED

(40 max.)

1

Aux. Pwr

Standby: 10 mA mA

Alarm: 220 mA

mA

LED: 10 mA mA

mA

SLC

Standby/Alarm: .55 mA mA

mA

SD500-SDM

(127 max.)

1

SLC

Standby/Alarm: .55 mA mA

mA

Aux. Pwr

Standby: 20 mA mA

Alarm: 106 mA

mA

SLC Accessory Bases

SD505-6RB

(127 max.)

Standby/Alarm: .082 mA mA

mA

SD505-6SB

(127 max.)

Aux. Pwr

Standby: 1 mA mA

Alarm: 32 mA

mA

SLC

Standby/Alarm: .082 mA mA

mA

SD505-DUCTR

(127 max.)

Aux. Pwr

Standby: 20 mA

2

mA

Alarm: 62 mA

2

mA

SLC

Standby/Alarm: .5 mA mA

mA

SD505-DTS-K

(127 max.)

None, included with SD505-DUCTR worst case.

SD505-DUCT

(127 max.)

SLC

Standby/Alarm: .5 mA mA

mA

SLC Isolator Devices

SD500-LIM

(254 max.)

Standby/Alarm: .092 mA mA

mA

SD505-6IB

(127 max.)

Accessories Modules

5860 Remote Fire Alarm
Annunciator

(12 max.)

Standby: 20 mA mA

Alarm: 65 mA

mA

5824 Serial/Parallel Printer
Interface

(2 max.)

Standby/Alarm: 45 mA mA

mA

5865-4 LED Annunciator
(with reset and silence switches)

(8 max.)

Standby: 35 mA mA

Alarm: 145 mA

mA

5865-3 LED Annunciator

Standby: 35 mA mA

Alarm: 145 mA

mA

5880 LED I/O Module

Standby: 35 mA mA

Alarm: 200 mA

mA

5883 Relay Interface

(32 max.)

Standby: 0 mA mA

Alarm: 220 mA

(22 mA per relay)

mA

5496 Notification Power Expander

(8 max.)

Standby/Alarm: 10 mA mA

mA

5895XL Intelligent Power Expander

Standby/Alarm: 10 mA mA

mA

5865-4 LED Annunciator
(with reset and silence switches)

(8 max.)

Standby: 35 mA mA

Alarm: 145 mA

mA

A

Total System Current

Auxiliary Devices

3

Refer to devices manual for current rating.

Alarm/Standby: mA mA

mA

Alarm/Standby: mA mA

mA

Alarm/Standby: mA mA

mA

B

Auxiliary Devices Current

Table 3-3: Current Draw worksheet for SD Devices

Device

Number of

Devices

Current per Device

Standby

Current

Alarm

Current

Advertising