Note: The following formulas were used to generate the wire distance chart:

Wiring Distance calculation example:

Suppose a system is configured with the following SBUS modules:

2 - Module 5860 Fire Annunciator

1 - 5496 Notification Power Expander

1 - 5865 LED Fire Annunciator

1 - 5824 Serial/Parallel Printer Interface Module

The total worst case current is calculated as follows:

Using this value, and referring to the Wiring Distance table, it can be found that the available options are:

370 feet maximum using 22 Gauge wire

938 feet maximum using 18 Gauge wire

1493 feet maximum using 16 Gauge wire

2362 feet maximum using 14 Gauge wire

Maximum Resistance (Ohms) =

6.0 Volts

Total Worst Case Current Draw (amps)

Maximum Wire Length (Feet) =

(6000 feet maximum)

Maximum Resistance (Ohms)

* 500

Rpu

where: Rpu = Ohms per 1000 feet for various Wire Gauges (see table below)

Table 4-2: Typical Wire Resistance Per 1000 ft. Using Copper Wire

Wire Gauge

Ohms per 1000 feet (Rpu)

22

16.2

18

6.4

16

4.02

14

2.54

5860 Current Draw

= 2 x .100 amps

= .200 amps

5496 Current Draw

= 1 x .010 amps

= .010 amps

5865 Current Draw

= 1 x .200 amps

= .200 amps

5824 Current Draw

= 1 x .040 amps

= .040 amps

Total Worst Case Current Draw

= .450 amps