5 flexputs™ i/o circuits, 1 conventional notification appliance, 2 releasing operations – SilentKnight 5895XL 6A Intelligent Remote Power Supply User Manual

Page 27: 1 class b notification wiring, Flexputs™ i/o, 1 class b notification wiring -7, 5 flexputs, I/o circuits

Advertising
background image

Hardware Installation

151142

3-7

3.5

Flexputs

I/O Circuits

The six Flexput™ circuits are an innovative and versatile feature of the 5895XL panel. They
can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4
wire detectors), or as auxiliary power (resettable, continuous, or door holder).

This section of the manual explains how to install conventional notification appliances and
initiating devices to be used with the 5895XL.

3.5.1

Conventional Notification Appliance

This sub-section of the manual explains how to install conventional notification appliances for
Class A (Style Z) and Class B (Style Y) configurations.

3.5.2

Releasing Operations

Approved releasing solenoids are list in Table 3-1

.

Do not mix cross alarming zones with

smoke verification zones. There must be at least two automatic detection devices in each
protected space. Spacing must be reduced to 0.7 times the linear spacing in accordance with
NFPA 72.

3.5.2.1 Class B Notification Wiring

You must use an appliance from the list of compatible appliances in the Appendix A.

To install a Class B notification appliance circuit:

1. Wire Class B Notification appliances as shown in Figure 3-8.

2. Configure the circuit through programming.

Figure 3-8 Class B Notification Appliance Circuit Wiring

Table 3-1: Approved Releasing Solenoids

Manufacturer

Part Number

Rating

Current

Freq

Asco

T8210A107

24 VDC

3A max

0 Hz

8210G207

24 VDC

3A max

0 Hz

Alarm

Polarity

UL Listed EOL

Model 7628

4.7 k

Supervised
Power Limited

Notification Wiring

Regulated