Hardware Installation

151142

3-13

Installing 4-Wire Class A Smoke Detectors

Figure 3-15 illustrates how to install 4-wire Class A detectors.

Conventions used for wiring 4-wire Class A loops:

1. Up to two Class A 4-wire loops can be connected to the control panel at once.

2. Smoke power is supplied to each Class A loop as shown in Figure 3-15.

Figure 3-15 Class A 4-Wire Smoke Detector Connections

Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit

number used. For example, Figure 3-15 uses I/O circuits 1, 2, 3 together and 4, 5, 6 together. In
programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4.

3.5.6

Auxiliary Power Configuration

Flexput circuits 1-6 on the control panel can be used as auxiliary power circuits. The three
types of auxiliary power available are:

Door Holder (see Section 3.5.6.1 for description)

Constant (see Section 3.5.6.2 for description)

Resettable (see Section 3.5.6.3 for description)

Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for
all Flexput circuits must not exceed 5A).

To configure a Flexput circuit as auxiliary power:

1. Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 3-16 for

location or Flexput circuits.