Ferrite bead installation, Figure 6 ipdact-2 and ipdact-2ud wiring, Figure 7 ferrite bead installation – SilentKnight IP Communicator User Manual
Page 8
8
IP Communicator Series Installation Document — P/N 53109:I 4/26/2010
Ferrite Bead Installation
A Ferrite Bead is required for the TO AP (smaller bead) to FACP Telco Line wires and for the IPDACT Series 24 VDC
(larger bead) Power Supply wires. Each wire must be wrapped twice around the Ferrite Bead at the end closest to
IPDACT Series board.
Note that the following illustration depicts one wire wrapped around the Ferrite Bead. The two wires to the TO AP termi-
nals must be wrapped around one, smaller Ferrite Bead and the -24 VDC and + 24 VDC wires must be wrapped around a
second, larger Ferrite Bead.
RJ45 Connector for connection to RS232 serial port.
Use a Serial to USB converter if the computer does not have an RS232 port.
(FOR PROGRAMMING USE ONLY)
2UD Modem Card
Supplied Phone Cable
Supplied Phone Cable
Ferrite*
(minimum wire
gauge 22-14 Awg)
(Note the the male plug connectors on the other end of the Supplied Phone
Cable, plug into the Primary and Secondary Phone Jacks on the FACP DACT.)
1K
Ω ELRs
(factory installed)
From FACP Nonresettable 24VDC (-)
From FACP Nonresettable 24VDC (+)
RJ45 Connector for connection to
Ethernet/Internet (minimum wire
gauge 24-22 Awg)
Ferrite*
(minimum wire gauge 18-14 Awg)
Figure 6 IPDACT-2 and IPDACT-2UD Wiring
* Refer to Figure 7 for Ferrite Bead Installation
The smaller ferrite bead is used on the “TO AP
connection.
The larger ferrite bead is used on the “24VDC”
connection.
ipd
a
c
t-
2b
rd
_2
UD.wmf
Figure 7 Ferrite Bead Installation
fer
ri
teipd
a
ct.
w
mf