Important information that you and your Central Station need to know

This document contains important information that you will need to know before you use the IP-
GSM communicator with Silent Knight fire alarm control panels. Please review this information
before sending transmissions to the central station.

Reporting Parameters:

When Silent Knight Addressable FACPs are configured to report by point, AlarmNet Contact ID,
the Group Value, will only allow a single digit. While with regular Contact ID, the Group is a two
digit value.

The point events send the Module information in the Group field and ranges from 1 to 99. See
examples below. The upper digit is always a 0 in the AlarmNet Contact ID datastream, so a Module
34 is actually sent as a 04.

Note: SLC Modules addresses report as 201-299

AlarmNet Receiver Output

5820XL, 5808, and 5700 Fire Panel

Contact ID data:

Panel Report by Point:

[10]00s9990s18sE320s04sC002s[13]

NAC Trouble Circuit 2 Module 34 Internal Supply

[10]00s9990s18sR320s04sC002s[13]

Restore NAC Trouble Circuit 2 Module 34 Internal Supply

[10]00s9990s18sE110s03sC043s[13]

Fire Alarm Pt. 43 Module 33-Internal SLC-Zone 1

[10]00s9990s18sR110s03sC043s[13]

Restore Fire Alarm Pt. 43 Module 33-Internal SLC-Zone 1

[10]1As3456s18sE200s03sC062s[13]

Supervisory Detector Pt. 62 Module 33-Internal SLC-Zone 2

[10]1As3456s18sR200s03sC062s[13]

Restore Supervisory Detector Pt. 62 Module 33-Internal SLC-
Zone 2

[10]1As3456s18sE115s03sC201s[13]

Manual Pull Pt. 01 Module 33-Internal SLC-Zone 3

[10]1As3456s18sR115s03sC201s[13]

Restore Manual Pull Pt. 01 Module 33-Internal SLC-Zone 3

[10]1As3456s18sE113s03sC202s[13]

Water Flow Pt. 02 Module 33-Internal SLC-Zone 4

[10]1As3456s18sR113s03sC202s[13]

Restore Water Flow point 02 Module 33-Internal SLC-Zone 4