Panel setup parameters when using the Honeywell IP-GSM
Communicator, Report by Point, with Silent Knight addressable
FACP’s:

IntelliKnight - Internal SLC Loop = Module 33, Internal Power Supply = Module 34

1. Addressable Panels should be set to report by Zone and not Point.

2. If set to report by Point, SLC Loop Expander SBUS Modules addressed should fall in the

following range.

5820XL - Modules 1, 2 and 4 thru 9. Avoid Module address 03 because internal SLC
will report as 03)

5808 and 5700 don't support External SLC Module addresses, so other expanders
should try and fall in the 1 thru 9 for SBUS Module addresses.