Slant/Fin VSPH-180 User Manual

Page 5

Advertising
background image

VENTING APPLICATION

VSPH Series are sealed combustion type boilers, they maybe

installed and vented either as a direct vent boiler which all air

for combustion is obtained directly from outside or as a non-

direct vent boiler which air for combustion is taken from inside

the boiler room.

VSPH boilers must be vented by proper 3" diameter stainless

steel venting system (see “vent material” on this page) through

the roof or sidewall.

BOILER ROOM AIR SUPPLY AND VENTILATION

An ample supply of air is required for combustion and ventila-

tion. When buildings are insulated, caulked and weather-

stripped, now or later on, direct openings to outside may be

required and should be provided. If the boiler is not near an

outside wall, air may be ducted to it from outside wall openings.

Provisions for combustion and ventilation air must be made in

accordance with section 5.3, Air for Combustion and Ventila-

tion, of the National Fuel Gas Code, ANSI Z223.1-latest edi-

tion, or applicable provisions of the local building codes. The

following recommendation applies to buildings of energy-saving

construction, fully caulked and weatherstripped.

INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES

TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR

INTO THE BOILER ROOM:

A. NON-DIRECT VENT INSTALLATION

1. Air drawn horizontally from outdoors DIRECTLY

through an outside wall; one louvered opening near the

floor and one louvered opening near the ceiling, each open-

ing with a minimum FREE air passage area of 1 square

inch per 4000 Btuh of total appliances’ input.

2.

Air drawn horizontally through HORIZONTAL DUCTS;

one opening near the floor and one opening near the ceil-

ing, each opening with a minimum FREE air passage area

of 1 square inch per 2000 Btuh of total appliances’ input.

3.

Air drawn VERTICALLY from outdoors; one opening at

the floor and one opening at the ceiling, each opening with

a minimum FREE air passage area of 1 square inch per

4000 Btuh of total appliances’ input.

4.

Air drawn from inside the building; one opening near

the floor and one opening near the ceiling, each opening

with a minimum FREE air passage area of 1 square inch

per 1000 Btuh of total appliances’ input.

IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL

BURNING EQUIPMENT, THE AREA OF FREE OPENINGS

MUST BE APPROPRIATELY INCREASED TO ACCOMMO-

DATE THE ADDITIONAL LOAD.

B. DIRECT VENT INSTALLATION

Adequate air supply should be provided to prevent overheating

of the boiler controls and boiler room. Openings for passage of

air into the boiler room for direct-vent installation must be at

least

1

2

of the openings required for the non-direct vent as men-

tioned above.

If additional non-direct vent appliances are installed in the same

space and adequate air openings are provided for them, there

are no additional air openings required for the VSPH boiler.

For both direct and non-direct installation, the following must be

considered:

-

Openings must never be reduced or closed. If doors or

windows are used for air supply, they must be locked

open.

-

Protect against closure of openings by snow and debris.

Inspect frequently.

-

No mechanical draft exhaust or supply fans are to be

used in or near the boiler area.

-

Boiler area must never be under negative pressure. The

flow of combustion and ventilating air to the boiler must

not be obstructed.

FLUE GAS VENTING REQUIREMENTS

The Victory VSPH series boiler is a high efficiency, mechanical-

ly induced draft boiler and, therefore, requires different venting

arrangements than natural draft, lower efficiency boilers.

THE FOLLOWING INSTRUCTIONS MUST BE CAREFULLY

READ AND FOLLOWED IN ORDER TO AVOID ANY HAZ-

ARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION

OF THE AIR INTAKE AND FLUE GAS VENTING SYSTEM.

The vent piping installation MUST be in accordance with these

instructions and with ANSI Z223.1-latest edition NATIONAL

FUEL GAS CODE, Part 7, Venting of Equipment. Other local

codes may also apply and must be followed. Where there is a

conflict between these requirements, the more stringent case

shall apply.

The use of a vent damper is NOT permitted on this boiler

series.

VENT MATERIAL

The vent system for direct or non-direct vent installation must

be UL listed single wall 3” diameter AL29-4C* stainless steel

material. The following manufacturers’ systems are approved

for use within a specified minimum and maximum equivalent

vent length for each model. Proper adapter must be used as a

connector between Victory VSPH boilers flue collar and venting

system as shown below:

Heat-Fab. Inc.

Saf-T Vent

Not required

RTV 106 or Dow

Corning 732

Heat-Fab. Inc.

Saf-T Vent

Not required

Not Required

EZ Seal

ProTech System,

FasNSeal

FSA-HFA3

Not Required

Inc.

Flex-L

StaR-34

SRASFA3

GE-IS806

International, Inc.

Z-Flex, Inc.

Z-Vent

O2SVSSLA2

GE, RTV 106

V

ICTORY VSPH Models

5

*AL29-4C is a registered Trademark of Allegheny Ludlum Corp

Manufacturer

Type/System

Adapter Part
No.

Sealant

Heat-Fab Part Numbers for various items of vent system are listed in
Slant/Fin Part List, Publication No. VSPH-10PL

Advertising
This manual is related to the following products: