Sc3/10 problem descriptions – Specialty Concepts SC3/10) User Manual

Page 11

Advertising
background image

SC3/10 PROBLEM DESCRIPTIONS

(from the SC3/10 PROBLEM CHART)

SC3/10 Case 1 - A continuous low voltage condition with good charging during the day

would indicate that the controller is functional but a problem exists with one of the
following:

A problem exists with the system sizing. See SYSTEM IS NOT SIZED CORRECTLY

(Help Note #5)

••

A problem exists with the solar panels. See SOLAR PANEL PROBLEM SECTION

••

A problem exists with the batteries. See BATTERY PROBLEM SECTION

SC3/10 Case 2 - A low voltage condition with no charging during the day would indicate

one of the following:

The system has no panel input. See BAD CONNECTION: PANEL (Help Note #8)

••

The SC3/10 may be defective. See CONTROLLER DEFECTIVE (Help Note #12)

SC3/10 Case 3 - A moderate voltage condition where the charging appears to stop too

soon (below 14.1 volts) would indicate one of the following:

••

The SC3/10 may have a bad battery connection. Somewhere in the battery

connection there could be a voltage drop that would cause the controller to sense
a higher battery voltage than what actually exists. See BAD CONNECTION:
BATTERY
(Help Note #9)

••

The SC3/10 may be defective. See CONTROLLER DEFECTIVE (Help Note #12)

TEST: - Try to monitor the voltage at the SC3/10 battery connection wires (Red and Black)

when the controller actually stops charging (CHARGING light goes OFF). If the
voltage at the SC3/10 terminals is about 14.3 volts then assume a voltage drop along
the battery connection is causing the problem.

SC3/10 Case 4 - A high voltage condition with additional charging would indicate one of

the following:

The battery voltage may be just under the charge termination set-point and not need

to shut off. See NORMAL OPERATION: CHARGING / NOT CHARGING (Help
Note #1)

The SC3/10 may be defective. See CONTROLLER DEFECTIVE (Help Note #12)

SC3/10 Case 5 - A high voltage condition (over 14.5 volts) with the solar charging

terminated during the day would indicate the controller is functional but the batteries are
being over-charged by a second charging source. Other charging sources should
feature their own charge regulation.

Advertising