Determine the location of the fireplace as

described in the fireplace installation manual. Then
plan the location of the duct termination and the route
of the duct run between the fireplace and the
duct termination.

Duct run must be limited to a maximum distance

of 40' (12.2m) from the fireplace pipe collar to duct
termination. This will provide the least restriction to air
flow. No more than four (4) 90º elbows can be used.
Duct run may be horizontal, vertical, inclined or any
combination of these. (Fig. 10) You are now ready to
install the Outside Air Kit.

1. Remove the screws retaining the outside air

coverplate, if provided. (Located on the left side of
front open units, on backside of multi-sided units.)
Discard coverplate. (Fig. 11)

2. Secure the inlet collar assembly to the outer casing

with four screws (screws not provided).

3. Slide the duct over the collar and attach the duct to

the collar using the plastic tie straps or three (3)
screws (screws not provided). Continue attaching
the ducting together using three (3) screws at each
joint until you have installed sufficient duct to arrive
at your duct termination locations.

4. At the termination end, install the duct termination.

This should be installed from the outside of the
home. Cut a hole in the desired location
approximately 4" in diameter, caulk around the
hole, and slide the termination through the opening
from outside the home. The termination/rain cap
should be caulked around its perimeter to assure
a tight seal. The rain cap opening should be
positioned downward.

The Outside Air Kit is now installed and ready

for use.

A

DETAIL A

Fig. 11

Ceiling

Duct

Duct
Termination

40ʼ Max

Duct Run

Soffit Termination

Exterior Wall Termination

Exterior Wall

40ʼ Max. Duct Run

Duct

Duct Termination

Rain Cap

Fig. 10

Soffit Termination

40' Max

Duct Run

Exterior Wall Termination

Exterior Wall

Rain Cap

40' Max. Duct Run

Duct

Duct Termination