Step 11 — Route VAV Static Pressure Sensors

VAV DUCT PRESSURE TRANSDUCER — The VAV duct

pressure transducer (VAV inverter pressure transducer) is locat-

ed behind the filter access door on the lower inner panel. See

Fig. 33. A section of field-supplied

1

/

4

-in. plastic tubing must

be run from the high pressure tap on the differential pressure

switch and connected to a field-supplied tap in the supply-air

duct. The tap is usually located

2

/

3

of the way out on the main

supply duct. Remove plug button in panel to route tubing.
VAV BUILDING PRESSURE TRANSDUCER — The VAV

building pressure transducer (modulating power exhaust pres-

sure transducer) is located behind the filter access door on the

lower inner panel. See Fig. 33. A section of field-supplied

1

/

4

-in. plastic tubing must be run from the high pressure tap on

the differential pressure switch to the conditioned space. The

pressure tube must be terminated in the conditioned space

where a constant pressure is required. This location is usually

in an entrance lobby so that the building exterior doors will

open and close properly. Remove plug button in panel to route

tubing.

The low pressure tap is factory-routed to the atmosphere.

For a positive-pressure building, route the high tap to building

air and low tap to atmosphere. For a negative-pressure

42.56”

42” MIN.

S/A

R/A

ECONOMIZER

HOOD

ECONOMIZER

HOOD

J BOX

PLENUM RATED
CABLE
(FIELD SUPPLIED)

12.94

(UNIT

OPENING)

NOTE: 020-050 SIZES SHOWN (2 POWER EXHAUST FANS).
SIZES 051 AND 060 HAVE 3 POWER EXHAUST FANS. ALL
UNIT SIZES HAVE THE SAME SIZE POWER EXHAUST.

“END #2”

“END #1”

ALTERNATE
LOCATION
(END)

23.28”

TYP

42.62

TYP

LOCATION
BAROMETRIC RELIEF
OR POWER EXHAUST
“SIDE #2”

23.28”

“SIDE #1”

42.62”

J BOX

R/A

S/A

Fig. 31 — Power Exhaust Relocated to Side Return Duct

a48-8244

NOTES:

1. Unless otherwise specified, all dimensions are to outside of part.
2. Dimensions are in inches.
3. On 48AW,AY units, accessory barometric relief or power exhaust must be mounted in the field-supplied return ductwork.

Fig. 32 — Barometric Relief Damper and Power Exhaust Mounting Details

a48-3808