building, route the high tap to atmosphere and the low tap to

building air.

Step 12 — Install All Accessories —

After all the

factory-installed options have been adjusted, install all field-

installed accessories. Refer to the accessory installation instruc-

tions included with each accessory.

The 48A Series units have a large number of factory-

installed options which were previously available only as

accessories. Some of the available options can also be installed

in the field if needed. In most cases the units have been

pre-wired so that the accessories can be easily installed.

Instructions are shipped with each accessory. Configuration of

the controls for these accessories as well as the factory-installed

options can be found in the Controls, Start-Up, Operation,

Service and Troubleshooting Book. The following is a list of

some of the common accessories:

• Thermostats and space temperature sensors

• LP (liquid propane) conversion kit

• Accessory barometric relief damper

• Accessory power exhaust

• Non-modulating to modulating power exhaust

• Condenser coil hail guards

• Outdoor humidity sensor (used for economizer enthalpy

changeover)

• Return air humidity sensors (used for economizer

differential enthalpy changeover)

• Return air smoke detector

• Controls expansion module (used for interface to build-

ing management systems, not typically needed on

system with the Carrier Comfort Network

®

[CCN] sys-

tem)

• Plugged filter sensor

• Motormaster® V low ambient head pressure control

Step 13 — Field Modifications

DUCTWORK
Bottom Return Units (48AJ and AK) Field-Modified for

Side Return — The 48AJ and AK units with bottom return air

connections may be field-modified to accommodate side return

air connections.

Conversion to horizontal return requires that the bottom

return openings of the unit must be sealed with airtight panels

capable of supporting the weight of a person. The return

ductwork connection locations on the side of the unit are higher

than normal (31-in. high). Unit-mounted power exhaust or

barometric relief cannot be used because of return air ductwork

will cover the power exhaust or barometric relief installation

locations. Power exhaust or barometric relief may be installed

in the return air ductwork.

To convert the unit, perform the following:

1. Seal the bottom return openings of the unit with airtight

panels capable of supporting the weight of a person.

2. Remove the panels located below the economizer

outdoor-air dampers. These openings will be used for the

return-air ductwork. There are 2 panels on 48AJ,AK020-

050 units. There are 3 panels on 48AJ,AK051 and 060

and units. These openings are normally used for power

exhaust or barometric relief.

3. Run the return air ductwork up to the openings. One

single duct is recommended to connect to the unit over

the return air openings. See Fig. 34. The return duct must

incorporate a minimum

3

/

4

-in. flange for connection to

the unit cabinet. The unit does not have duct flanges for

this conversion.

Side Supply and Return Units (48AW,AY) with Field-

Installed Power Exhaust in Return Duct — Space must be

available in the return duct to mount the power exhaust fan

(gravity relief) modules. Dimensions and suggested locations

are shown in Fig. 34. These instructions are a guideline and not

a comprehensive procedure. The design contractor must pro-

vide some design initiative.

The wiring harness that is provided with the power exhaust

accessory is not long enough for the fan modules to be mount-

ed in the return air duct. Field-supplied wiring must be spliced

into the harness. Use a junction box at each splice. The wiring

may be run in the return duct, or externally in conduit. A ser-

vice access panel will be needed near each power exhaust fan.

IMPORTANT: Carrier recommends the installation of

field-fabricated wind baffles on all vertically oriented

condenser coils when operating in environments with

prevailing winds of more than 5 MPH and where tem-

peratures drop below 32 F. See the Motormaster

accessory installation guide for instructions.

IMPORTANT: The following section is a guideline and not

a comprehensive procedure to field modify the units. The

installing contractor must provide some design initiative.

Field-conversion is complex and is not recommended.

Units with electric heat must not be converted because of

potential heating mode operating problems.

AUXILIARY
CONTROL BOX

PRESSURE TRANSDUCERS
(INSIDE OF PANEL)

Fig. 33 — Pressure Transducer Locations

a48-6976