Sure Heat CVS303 LP Conversion User Manual

Page 2

Advertising
background image

Sure Heat Manufacturing • 1861 West Oak Parkway • Marietta, GA • 30062• 1-800-229-5647

DUAL BURNER LOG SETS

A. Replace the Natural Gas Orifice (Part #20) included in the Safety Pilot Kit (Model CVS-303) with

the L.P. Air Shutter Orifice. This kit contains (2) L.P Air Shutter Orifices, Part A and Part B. The

orifice with the small inner hole is used on the 18” Log Sets. The orifice with the larger hole is

used on 24” and 30” log sets. Be sure to attach the short stem on the appropriate L.P. Air Shutter

Orifice directly to the Burner System for proper operation. (See Figure 1)

NOTE: Refer to the Safety Pilot Valve instructions supplied with the Model CVS-303 for

detailed instructions on pilot installation.

B. Replace the Natural Gas Pilot Burner Orifice with the L.P./ Propane Orifice (Part D) supplied with

this kit.

1. Remove Pilot Supply Line Nut (Part #14) from the Pilot Burner (Part #7). Replace Natural

Gas Orifice with the L.P. Gas Orifice (Part D) included with this conversion kit.

NOTE: Refer to the detailed Safety Pilot Illustration on front cover for placement

of the L.P. Pilot Orifice.

C. Replace Heavy Media (Granules) supplied with the Natural Gas Log set with Vermiculite

Granules, sold separately. DO NOT USE Heavy Media Granules as improper combustion will

occur. After the Vermiculite Bed has been put in place, spread the Glowing Embers (insulation

type material) supplied with the Gas Log Set over the Vermiculite Bed.

3/8” Locknut is

included with the

gas log sets

Figure 1