50KQL12 — NOMINAL AIRFLOW 350 CFM

LEGEND

*ARI 320 points (bold printing) are shown for comparison purposes

only. These are not certified data points.

NOTES:

1. MOPD = Maximum Operating Pressure Differential (water pres-

sure differential at unit cannot exceed MOPD or water valve can-
not close)

2. Interpolation is permissible, extrapolation is not.
3. All entering air conditions are 80 F db and 67 F wb in cooling and

70 F db in heating.

4. All performance data is based upon the lower voltage of dual volt-

age rated units. See Performance Correction Tables on page 21
for operating conditions other than those listed above.

5. ARI/ISO 13256-1 (WLHP application) certified conditions are 86 F

EWT, 80.6 db and 66.2 F wb in cooling and 68 F EWT, 68 F db and
59 F wb in heating.

EWT

(F)

GPM

WATER PRESSURE DROP (ft wg)

COOLING — EAT 80 F DB/67 F WB

HEATING — EAT 70 F

Without Motorized

Valve

With Cv = 2.9

MOPD = 125 psi

TC

SC

SHR

Input

Power

THR

TC

Input

Power

THA

20

1.6

2.1

6.5

Operation not recommended

Operation not recommended

2.3

3.8

11.4

3.1

6.1

19.6

8.7

0.78

6.0

30

1.6

1.8

6.5

14.8

9.8

0.66

0.60

16.8

9.4

0.81

6.6

2.3

3.3

11.4

14.9

9.9

0.66

0.55

16.8

9.7

0.83

6.9

3.1

5.3

19.6

15.0

9.9

0.66

0.53

16.8

9.9

0.83

7.1

40

1.6

1.6

6.5

14.4

9.6

0.67

0.68

16.7

10.6

0.86

7.7

2.3

3.1

11.4

14.7

9.7

0.66

0.62

16.8

11.0

0.87

8.0

3.1

4.8

19.6

14.8

9.8

0.66

0.59

16.8

11.2

0.88

8.3

50

1.6

1.6

6.5

14.0

9.5

0.68

0.76

16.6

11.8

0.89

8.8

2.3

2.9

11.4

14.3

9.6

0.67

0.70

16.7

12.3

0.91

9.2

3.1

4.5

19.6

14.5

9.6

0.67

0.67

16.7

12.6

0.92

9.5

60

1.6

1.5

6.5

13.5

9.3

0.69

0.86

16.4

13.1

0.93

9.9

2.3

2.7

11.4

13.8

9.4

0.68

0.79

16.5

13.6

0.94

10.4

3.1

4.3

19.6

14.0

9.5

0.68

0.76

16.6

13.9

0.95

10.7

70

1.6

1.4

6.5

12.9

9.1

0.71

0.97

16.2

14.3

0.96

11.0

2.3

2.6

11.4

13.3

9.2

0.69

0.90

16.3

14.9

0.97

11.6

3.1

4.1

19.6

13.5

9.3

0.69

0.86

16.4

15.2

0.98

11.9

80

1.6

1.3

6.5

12.2

8.9

0.73

1.10

15.9

15.5

0.98

12.1

2.3

2.5

11.4

12.7

9.0

0.71

1.01

16.1

16.0

0.99

12.7

3.1

3.9

19.6

12.9

9.1

0.71

0.97

16.2

16.3

1.00

12.9

85

1.6

1.3

6.5

11.8

8.8

0.74

1.16

15.8

16.0

0.99

12.6

2.3

2.4

11.4

12.3

8.9

0.72

1.07

16.0

16.6

1.00

13.2

3.1

3.8

19.6

12.6

9.0

0.72

1.03

16.1

16.9

1.01

13.4

90

1.6

1.3

6.5

11.5

8.6

0.75

1.23

15.7

16.5

1.00

13.1

2.3

2.3

11.4

12.0

8.8

0.73

1.14

15.8

17.1

1.01

13.6

3.1

3.7

19.6

12.2

8.9

0.73

1.09

15.9

17.3

1.01

13.9

100

1.6

1.2

6.5

10.7

8.4

0.78

1.37

15.4

Operation Not Recommended

2.3

2.2

11.4

11.2

8.6

0.76

1.27

15.6

3.1

3.4

19.6

11.5

8.6

0.75

1.23

15.7

110

1.6

1.1

6.5

9.9

8.1

0.82

1.52

15.1

2.3

2.0

11.4

10.4

8.3

0.79

1.42

15.3

3.1

3.2

19.6

10.7

8.4

0.78

1.37

15.4

DB

Dry Bulb

EAT

Entering Air Temperature (F)

EWT

Entering Water Temperature (F)

GPM

Gallons per Minute

MBtuh — Btuh in Thousands
SC

Sensible Capacity (MBtuh)

SHR

Sensible Heat Ratio

TC

Total Capacity

THA

Total Heat of Absorption (MBtuh)

THR

Total Heat of Rejection (MBtuh)

WB

Wet Bulb

WLHP — Water Loop Heat Pump

Performance data (cont)