Remote-mounted thermostat with deluxe d controller, Typical wiring schematics (cont) – Carrier AQUAZONE 50KQL-1PD User Manual

Page 30

Advertising
background image

30

Typical wiring schematics (cont)

AL

Alarm Relay Contacts

BR

Blower Relay

CAP

Capacitor

CB

Circuit Breaker

CO

Sensor, Condensate Overflow

CR

Compressor Relay

DM

Damper Motor

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

FSS

Fan Speed Switch

HP

High-Pressure Switch

JW1

Jumper Wire for Alarm

LOC

Loss of Charge Pressure Switch

NLL

Night Low Limit

PB

Power Terminal Block

PBS

Push Button Switch

PM

Performance Monitor

RVS

Reversing Valve Solenoid

TRANS — Transformer
WV

Water Valve

----------

Field Line Voltage Wiring
Field Low-Voltage Wiring

REMOTE-MOUNTED THERMOSTAT WITH DELUXE D CONTROLLER

Printed Circuit Trace

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lock

>>

CLOSED=UNOCCUPIED

Y

G

DELUXE

D

CONTROL

BR 1

(LO)

CR

CAP

PB

GROUND

LUG

TRANSFORMER

BR 2

(HI)

COMPR.
RELAY

CCG

YEL

HP

LOC

FP1

FP2

RV

CO12

P7

24V
DC

EH1
EH2

P6

HP

LOC

FP1

FP2

RVS

CO

SEE
NOTE
4

RED
RED
BLU
BRN
GRY
GRY
VIO
VIO
BRN
ORG
NOT USED

1
2
3
4
5
6
7
8
9

10

CC

BRN

YEL

CR

1

0

STATUS

DELUXE D

MICROPROCESSOR

CONTROL LOGIC

TEST

FAULT R

RV

RELAY

TEST

PINS

JW3
FP1 LOW
JW2
FP2 LOW

SEE
NOTE 4

JW1
LP N.O.

COM

NO

NO

NC

COM

FAN

SPEED

RELAY

FAN ENABLE

RELAY

GRY

Y1

Y1

W1

O/W2

G

R
C

AL1

COMPRESSOR

COOLING

FAN

24 VAC

COMMON

ALARM

CLASS 1 WIRING
REQUIRED INSIDE

Y

O

G

R

C

X1

CLASS 1 OR 2 WIRING
ACCEPTABLE
OUTSIDE
CONTROL BOX

TYPICAL HEAT

PUMP T-STAT

SEE NOTE 5

BRN

SEE

NOTE 7

AL2

R

NSB

C

ESD

OVR

H
A

R

NO1

NC1

COM

NO2
NC2

COM

R

P1

P2

P3

RED

BRN

WHT

YEL

RED

YEL

YEL

YEL

BRN

BRN

ORG

DM

OV

OV

OVERRIDE
OVERRIDE

OVERRIDE

WITH DIGITAL T-STAT

TIME CLOCK

NLL

WV

ALARM

RELAY

SEE

NOTE 6

C

R

JW4

AL2 DRY

COM2 COM1

R C S

S

C

1
2
3
4
5
6
7
8

ACC1

RELAY

ACC2

RELAY

BLU

S1

DIP SWITCH

PACKAGE

PM: DISABLE/
ENABLE
UNIT STAGE: 2/1
T-STAT: HEAT COOL/
HEAT PUMP
RV ON B/RV ON O
DEHUMID/NORMAL
NOT USED
BOILERLESS:
ENABLE/DISABLE
BOILERLESS:
40

°F/50°F

1

2
3

4
5
6
7

8

OFF ON

S2

DIP SWITCH

PACKAGE

ACC1
FUNCTIONS

ACC2
FUNCTIONS
H: HI FAN/DEHUMID
NOT USED

1
2
3
4
5
6
7
8

OFF ON

BLK

ORG
230V

24V

TRANS

CB*

POWER SUPPLY

REFER TO DATA PLATE

USE COPPER CONDUCTORS ONLY.

SEE NOTE 2

REFER TO DISCONNECT

BOX FOR OPTIONAL

POWER SUPPLY CONNECTION

GROUND

L2

L1

OPTIONAL
CORD
CONNECTION

RED

NEUTRAL ON 265V
SYSTEMS

L2 (ribbed)

GROUND

L1 (plain)

PB
1

2

H

C

F

CAP

RED

RED

6

8

2

4

BLK

BLK

R

S

C

CR

BLU

COMPRESSOR

BRN

YEL

2

1

BM

B (HIGH)

A (LOW)

RED

BLK

115
208
230
265

WHT
RED
ORG
BRN

LEAD COLOR

VOLTAGE

TRANSFORMER PRIMARY

LEAD COLORS

YEL

SEE
NOTE 3

1

3

2

FSS

GRY

LEGEND

BLOWER MOTOR WIRING

UNIT SIZE POLE A POLE B

07

5

3

09

5

4

12

4

3

15

4

3

19

4

3

*Optional wiring.

NOTES:

1. Compressor and blower motor thermally protected

internally.

2. All wiring to the unit must comply with local codes.
3. Transformer is wired to 115-V (WHT) lead for 115/1/60

units, 265-V (BRN) lead for 265/1/60 units or 208-V
(RED) lead for 208/1/60 units.
For 203/1/60 switch RED and ORG leads at L1 and
insulate RED lead.
Transformer is energy limiting or may have circuit
breaker.

4. FP1 thermistor provides freeze protection for WATER.

When using ANTI-FREEZE solutions, cut JW3 jumper.

5. Typical heat pump thermostat wiring shown. Refer to

thermostat Installation Instructions for wiring to the
unit.

6. 24-V alarm signal shown. For dry alarm contact, cut

AL2 DRY (JW4) jumper and dry contact will be avail-
able between AL1 and AL2.

7. Transformer secondary ground via Deluxe D board

standoffs and screws to control box. (Ground available
from top two standoffs as shown.)