Prestige TriMax Boiler Manual Addendum

The drain line materials must be an ap-

proved material by the authority having

jurisdiction. In absence of such authority,

PVC and CPVC piping must comply with

ASTM D1785 or D2845. The cement and

primer used on the piping must comply

with ASME D2564 or F493. For installa-

tions in Canada, use CSA or ULC certi-

fied PVC or CPVC pipe, fittings and

cement/primer.

8. Continue the pipe from the drain assembly

to a floor drain or condensate pump.

When selecting and installing a condensate

pump, ensure the pump is approved for use

with condensing boilers and furnaces. The

pump should be equipped with an overflow

switch to prevent property damage from

potential condensate spillage.

9. The PRESTIGE will typically produce a con-

densate that is considered slightly acidic

with a pH content below 3.0. Install a neu-

tralizing filter if required by authority hav-

ing jurisdiction.

The condensate drain must remain filled

and unobstructed and allow unrestricted

flow of condensate. The condensate

should not be subject to conditions where

freezing could occur. If the condensate is

subjected to freezing or becomes ob-

structed , it can leak, resulting in potential

water damage to the boiler and surround-

ing area.

NOTICE

CAUTION

NOTICE

Flexible Tubing

(or 3/4 PVC/

CPVC Piping

to Drain)

Compression

Nut with Rubber Seal

Fill Plug

with Vaccum

Break Port

Condensate

Drain Assembly

Plastic Ball

(Not shown)

Retaining Nut

Place the Metal Washer

and (2) Rubber Gaskets

in this Order for Proper

Seal.

Fig. 14: Condensate Drain Assembly

Date: 7/25/2013

2013-30 Prestige TriMax_Manual-Addendum