INSTALLATION

(continued)

1--2

Engine Starting Contacts

The engine control contact connections are located on the
transfer switch. Connect signal wires to appropriate term–

inals as specified in Table A, shown in Figure 1–2.

Table A. Engine start connections.

When normal source

fails

Terminals on transfer

switch

contact closes

TB14 and TB15

contact opens

TB14 and TB16

Transfer Switch

Figure 1-2. Engine starting contact label and location

for 260 and 400 amp. E–design transfer switches.

Controller Ground

A grounding wire must be connected to the controller’s
lower left mounting stud. Because the controller is

mounted on the enclosure door, a conductive strap must be

used between the enclosure and the door. This connection
provides proper grounding which does not rely upon the

door hinges.

Harnesses

The transfer switch is connected to the left side of the

controller by a plug–in harness (two plugs).

Auxiliary Circuits

Connect auxiliary circuit wires to appropriate terminals on

transfer switch. Note the control features that are fur-

nished on this switch. Make the necessary auxiliary
connections by referring to Section 5, Control Features.

Connections to Controller for other Control Features (located on bottom of Controller):

for factory

use only

Remote Control Features Connections

(refer to the Wiring Diagram &

page 5–5 for DIP switch settings)

Each control contact must be suitable

for a 5 V DC low energy circuit.

Programmable

Engine Exerciser

connection,

if provided

(refer to

page 5–2)

Load Disconnect

Feature

Connections

(see Wiring Diagram

& refer to page 5–5

for DIP switch settings)