04: Output parallel function setting

Interface Setting

When UPS input lines are not in parallel (Jumper between input L1 and input
L2 is removed), MENU 04 will be not available since outputs cannot be
connected in parallel.
Under this situation MENU 04 will show as reserved (not available) = RES
RES.

When UPS inputs are connected in parallel (jumper connected between input
L1 & input L2), UPS outputs can be configured as 1 output line (output L1 &
output L2 in parallel) or 2 separate output lines. This configuration requires to
set parameter 03 and 04 of MENU 04.

Parameter 2:
OP.P
means output 1 and output 2 parallel function.

Parameter 3:

DIS: disable output parallel function. Under this configuration output 1 and 2
must NOT be connected in parallel.
ENA: enable output parallel function to allow connecting 2 outputs in parallel to
get only one phase output with 100% of total UPS capacity. It is MANDATORY to
use one phase input connection when one phase output is required.
NOTE: If ENA is configured and 2 different outputs configuration is used this
setting will be ignored.

05: Voltage range for bypass

Interface Setting

Parameter 2: Set the acceptable low voltage for bypass. Setting range is from 60V
to 99V and the default value is 60V.
Parameter 3: Set the acceptable high voltage for bypass. Setting range is from
131V to 140V and the default value is 140V.

06: Frequency range for bypass

Interface Setting

Parameter 2: Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3: Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.

07: ECO mode enable/disable

Interface Setting

Parameter 3: Enable or disable ECO function. You may choose following two
options:
DIS: disable ECO function
ENA: enable ECO function
If ECO function is disabled, voltage range and frequency range for ECO mode still
can be set, but it is meaningless unless the ECO function is enabled.

08: Voltage range for ECO mode

Interface Setting

Parameter 2: Low voltage point in ECO mode. The setting range is from 5% to
10% of the nominal voltage.

Parameter 3: High voltage point in ECO mode. The setting range is from 5% to
10% of the nominal voltage.