TROUBLESHOOTING

PROBLEM DESCRIPTION

PROBABLE ROOT CAUSE

SUGGESTED ACTION

* LCD does not show input voltage value
* AC input failure alarm active
(1 beep / 4s) however AC input source is OK

Input power cord is not connected

Check input power cord connection.

Input power cord is connected into UPS
outlet.

Check input power cord connection.

UPS cannot be powered on even AC input is OK.
Beep alarm (1 beep/s) & LCD shows:

EP

EPO function is active.

Re-establish emergency power off
switch and set UPS in normal mode.

UPS cannot be powered on even AC input is OK.

ON push button is not been selected
properly

Push ON button during 2 seconds or
longer

1 beep / s alarm is active and LCD shows:

Internal or external batteries are not
properly connected

Check battery connection.

* Code: 02
* 1 beep / s

Input Neutral not connected or input
phase fuse open.

Check input Neutral connection. Reset
alarm in parameter 03 on LCD. If input
phase fuse is broken replace it.

* Intermittent:

+

* 2 beeps per second.

UPS overloaded

Disconnect devices from UPS outlets
until solving overload

* Intermittent:

+

* 2 beeps per second.
* By-Pass activated

UPS overloaded. UPS has changed to

BYPASS mode to avoid internal
damage.

Disconnect devices from UPS outlets

until solving overload

After repetitive small overloads, UPS

has changed to BYPASS mode.

Disconnect devices from UPS until

solving overload. Then power off UPS
and re-star it.

* Code 43

* Active:
* Continuous beep

UPS has been automatically powered

off because overload.

Disconnect devices from UPS outlets

until solving overload. Then power ON.

* Code 14, 15 or 17
* Active:

* Continuous beep

UPS has been automatically powered

off because short circuit detected at
output.

Check short circuit problem in devices

connected to UPS

* Intermittent: +

3F

* 1 beep / s

Parallel communication lost.

Check parallel cables and PAR 00X text
on each LCD. If problem is solved reset

alarm with UP and DOWN simultaneous
key selection.

* Any of the error codes activated

Probable internal UPS failure.

Contact service center.

Backup time is lower than expected

Batteries are not fully charged or maybe
they are worn out.

Let UPS recharge batteries during 6
hours. If it does not solve the problem
batteries maybe need to be replaced.