step 3 — Field Fabricate Ductwork

— Secure all

ducts to building stnjcture. Use flexible duct connectors be­
tween unit and ducts as required. Insulate and weatlierproof all
external ductwork, joints, and roof openings with counter

flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be in­

sulated and covered with a vapor barrier.

Step 4

Make Unit Duct Connections

— Unit

is shipped for thra-the-bottom duct connections. Ductwork

openings are shown in Fig. 1, 4, and 5. Duct connections are

shown in Fig. 6. Field-fabricated concentric ductwork may be

connected as shown in Fig. 7 and 8. Attach all ductwork to roof
curb and roof cuit) basepans.

Step 5 — Install Flue Hood and Wind Baffle —

Flue hood and wind baffle are shipped secured under main
control box. To install, secure flue hood to access panel. See
Fig. 9. The wind baffle is then installed over the flue hood.

NOTE: When properly installed, flue hood will line up with
combustion tan housing. See Fig. 10.

Step 6

Trap Condensate Drain

— See Fig.

1 1

for drain location. One ^

4

-in. half coupling is provided inside

unit evaporator section for condensate drain connection. An
S'A-in.

X

^

4

-in. diameter and 2-in.

x

diameter pipe nip­

ple, coupled to standard V

4

-in. diameter elbows, provide a

straight path down through hole in unit base rtiils (see Fig. 12).
A trap at least 4-in. deep must be used.

NOTE: Do not drill in this area; damage to basepan may result in

water leak.

Fig. 6 — Air Distribution — Thru-the-Bottom

NOTE:

Dimensions

A,

A',

and

B'

are

obtained

trom

field-supplied

ceiling diffuser.

I

r| Shaded area indicates block-off panels.

Fig. 8 — Concentric Duct Details

AIR OUT

AIR IN

AIR OUT

NOTE: Do not drill in this area; damage to basepan may result in

water leak.

Fig. 7 — Concentric Duct Air Distribution